Screens Sample Clauses
Screens. 3.2.1.1 The proposed Generating Facility’s Point of Interconnection must be on, connected through the Interconnection Customer’s premises wiring and electric facilities to, a portion of GUC’s Electric Distribution System.
3.2.1.2 Interconnection of the proposed Generating Facility is in compliance with the North Carolina Eastern Municipal Power Agency (NECMPA) Regarding Generation on Participant Distribution Systems.
3.2.1.3 For interconnection of a proposed Generating Facility to a radial distribution circuit, the aggregated generation, including the proposed Generating Facility, on the circuit shall not exceed fifteen percent (15%) of the line section annual peak load as most recently measured at the substation. A line section is that portion of GUC’s System connected to a customer bounded by automatic sectionalizing devices or the end of the distribution line.
3.2.1.4 For interconnection of a proposed Generating Facility to the load side of spot network protectors, the proposed Generating Facility must utilize an inverter-based equipment package and, together with the aggregated other inverter-based generation, shall not exceed the smaller of five percent (5%) of a spot network’s maximum load or 50 kW.1
3.2.1.5 The proposed Generating Facility, in aggregation with other generation on the distribution circuit, shall not contribute more than ten percent (10%) to the distribution circuit’s maximum fault current at the point on the high voltage (primary) level nearest the proposed point of change of ownership.
1 A spot network is a type of distribution system found within modern commercial buildings to provide high reliability of service to a single customer. (Standard Handbook for Electrical Engineers, 11th edition, Xxxxxx Xxxx, XxXxxx Xxxx Book Company.)
3.2.1.6 The proposed Generating Facility, in aggregate with other generation on the distribution circuit, shall not cause any distribution protective devices and equipment (including, but not limited to, substation breakers, fuse cutouts, and line reclosers), or Interconnection Customer equipment on the system to exceed eighty seven and one half percent (87.5%) of the short circuit interrupting capability; nor shall the interconnection be proposed for a circuit that already exceeds eighty seven and one half percent (87.5%) of the short circuit interrupting capability.
3.2.1.7 Using the table below, determine the type of interconnection to a primary distribution line. This screen includes a review of the t...
Screens. 3.3.1 The proposed Generating Facility’s Point of Interconnection must be on a portion of the Cooperative’s Distribution System.
3.3.2 For interconnection of a proposed Generating Facility to a radial distribution circuit, the aggregated generation on the circuit, including the proposed Generating Facility, shall not exceed 15% of the line section annual peak load as most recently measured at the substation. A line section is that portion of a Cooperative’s System connected to a Member bounded by automatic sectionalizing devices or the end of the distribution line.
3.3.3 The proposed Generating Facility, in aggregation with other generation on the distribution circuit, shall not contribute more than 10% to the distribution circuit’s maximum fault current at the point on the high voltage (primary) level nearest the proposed point of change of ownership.
3.3.4 The proposed Generating Facility, in aggregate with other generation on the distribution circuit, shall not cause any distribution protective devices and equipment (including, but not limited to, substation breakers, fuse cutouts, and line reclosers), or Interconnection Member equipment on the system to exceed 87.5% of the short circuit interrupting capability; nor shall the interconnection be proposed for a circuit that already exceeds 87.5% of the short circuit interrupting capability.
3.3.5 The table below will be used to determine the type of interconnection to a primary distribution line. This screen includes a review of the type of electrical service provided to the Interconnection Member, including line configuration and the transformer connection to limit the potential for creating over-voltages on the Cooperative’s System due to a loss of ground during the operating time of any anti-islanding function. Three-phase, three wire Three-phase or single-phase, phase-to-phase FAIL Screen Three-phase, four wire Effectively-grounded three-phase or single-phase, line-to-neutral PASS Screen
3.3.6 If the Generating Facility system is integrated with storage, the inverter must be certified so as to rule out any risk of backfeeding.
3.3.7 If the proposed Generating Facility is to be interconnected on single-phase shared secondary, the aggregate generation capacity on the shared secondary, including the proposed Generating Facility, shall not exceed 25 kW.
3.3.8 If the proposed Generating Facility is single-phase and is to be interconnected on a center tap neutral of a 240 volt service, its addition shall no...
Screens. Lessees agree they will not remove screens from window or throw anything out of windows at any time.
Screens. Are located in the line between the scum gutter and the balance tank to collect all large floating or suspended matter such as grass, cloth, ice cream sticks, etc. Another screen is situated between the balance tank and the main circulating pump to prevent foreign matter getting into the pump. All screens should be cleaned regularly. Depending on the pool loading it may be necessary to do this every hour, it is important that these screens be cleaned at least daily.
Screens. 2.1.1 For interconnection of a proposed Customer-owned renewable generation system to a radial distribution circuit, the aggregated generation, including the proposed Customer- owned renewable generation, on the circuit shall not exceed 15 % of the line section annual peak load as most recently measured at the substation. A line section is that portion of FPL’s electric system connected to a Customer bounded by automatic sectionalizing devices or the end of the distribution line.
2.1.2 For interconnection of a proposed Customer-owned renewable generation system to the load side of spot network protectors, the Customer-owned renewable generation system must utilize an equipment package in compliance with the terms of the Interconnection Agreement.
2.1.3 The proposed Customer-owned renewable generation system, in aggregation with other generation on the distribution circuit, shall not contribute more than 10 % to the distribution circuit's maximum fault current at the point on the high voltage (primary) level nearest the proposed Point of Interconnection/Change of Ownership.
2.1.4 The proposed Customer-owned renewable generation system, in aggregate with other generation on the distribution circuit, shall not cause any distribution protective devices and equipment (including, but not limited to, substation breakers, fuse cutouts, and line reclosers), or Customer equipment on the system to exceed 87.5% of the short circuit interrupting capability; nor shall the interconnection be proposed for a circuit that already exceeds 87.5% of the short circuit interrupting capability.
2.1.5 Using the table below, determine the type of interconnection to a primary distribution line. This screen includes a review of the type of electrical service provided to the Customer, including line configuration and the transformer connection to limit the potential for creating over-voltages on FPL's electric power system due to a loss of ground during the operating time of any anti-islanding function.
Screens. 32.2.2.1.1 The proposed Small Generating Facility’s Point of Interconnection must be on a portion of the Connecting Transmission Owner’s Distribution System.
32.2.2.1.2 For interconnection of a proposed Small Generating Facility to a radial distribution circuit, the aggregated generation, including the proposed Small Generating Facility, on the circuit shall not exceed 15% of the line section annual peak load as most recently measured at the substation. A line section is that portion of a Connecting Transmission Owner’s electric system connected to a customer bounded by automatic sectionalizing devices or the end of the distribution line.
Screens. Where reasonably practical, having regard to heights, the Buyer must screen under any high-set house so that the underside of the house cannot be seen from the road frontage. The Buyer must screen by way of vegetation all water tanks so that they are not visible from the road frontage.
Screens. 3.2.1.1. The proposed Generating Facility’s Point of Interconnection must be on a portion of the Cooperative's Distribution System.
3.2.1.2. For interconnection of a proposed Generating Facility to a radial distribution circuit, the aggregated generation, including the proposed Generating Facility, on the circuit will not exceed 15% of the line section annual peak load as most recently measured at the substation. A line section is that portion of a Cooperative’s System connected to a customer bounded by automatic sectionalizing devices or the end of the distribution line.
3.2.1.3. For interconnection of a proposed Generating Facility to a radial distribution circuit, the aggregated generation, including the proposed Generating Facility, on the circuit will not exceed 90% of the circuit and/or bank minimum load at the substation.
3.2.1.4. All synchronous and induction machines must be connected to a distribution circuit where the local minimum load to generation ratio on the circuit line segment is larger than 3 to 1. A 3-1 load to generation ratio screen utilizes actual recorded data that is sufficient to establish the minimum threshold.
3.2.1.5. For interconnection of a proposed Generating Facility to the load side of spot network protectors, the proposed Generating Facility must utilize an inverter-based equipment package and, together with the aggregated other inverter- based generation, will not exceed the smaller of 5% of a spot
3.2.1.6. The proposed Generating Facility, in aggregation with other generation on the distribution circuit, will not contribute more than 10% to the distribution circuit's maximum fault current at the point on the high voltage (primary) level nearest the proposed point of change of ownership.
3.2.1.7. The proposed Generating Facility, in aggregate with other generation on the distribution circuit, will not cause any distribution protective devices and equipment (including, but not limited to, substation breakers, fuse cutouts, and line reclosers), or Interconnection Customer equipment on the system to exceed 87.5% of the short circuit interrupting capability; nor will the interconnection be proposed for a circuit that already exceeds 87.5% of the short circuit interrupting capability.
3.2.1.8. Using the table below, determine the type of interconnection to a primary distribution line. This screen includes a review of the type of electrical service to be provided to the Interconnection Customer, including line configuration an...
Screens replace or repair : cost to tenant is time plus materials
Screens. For interconnection of a proposed Customer-owned renewable generation system to a radial distribution circuit, the aggregated generation, including the proposed Customer- owned renewable generation, on the circuit shall not exceed 15 % of the line section annual peak load as most recently measured at the substation. A line section is that portion of FPL’s electric system connected to a Customer bounded by automatic sectionalizing devices or the end of the distribution line.