SPECIAL INSPECTION AND TESTING Sample Clauses

SPECIAL INSPECTION AND TESTING. Unless specifically set forth in this Contract, orders requiring special inspection and testing are subject to price adjustment to reflect the increased cost.
AutoNDA by SimpleDocs
SPECIAL INSPECTION AND TESTING. Inspection of Fabricators (OSSC 1704.2.5) Steel Construction (OSSC 1705.2) Concrete Construction (OSSC 1705.3) Masonry Construction (OSSC 1705.4) Wood Construction (OSSC 1705.5) Soils (OSSC 1705.6) Driven Deep Foundations (OSSC 1705.7) Cast-in-place Deep Foundations (OSSC 1705.8) Helical Pile Foundations (OSSC 1705.9) Sprayed Fire-resistant Materials (OSSC 1705.14) Mastic and Intumescent Fire-rest. Coatings (OSSC 1705.15) EIFS (OSSC 1705.16) Fire-Resist Penetrations and Joints (OSSC 1705.17) Post-Installed Anchors in Concrete (OSSC 1705.1.1)
SPECIAL INSPECTION AND TESTING. The (Name of Organization) shall provide the DNR written notification at a minimum of forty-eight hours in advance in advance of any special inspections or testing at the construction site. Copies of all inspection and test reports shall be provided to the DNR.
SPECIAL INSPECTION AND TESTING. The Architect shall establish the extent of the testing and special inspection program consistent with the applicable codes and needs of the particular project and shall issue specific instructions to the Project Manager, the Project Inspector and the testing facility and Special Inspectors prior to start of construction. The Project Inspector shall also notify Project Manager as to the disposition of materials noted on laboratory testing, and/or special inspection, reports as not conforming to the Judicial Council approved documents. The Judicial Council will select and contract for a Laboratory to conduct all special inspections and materials testing; costs for all special inspections and materials testing will be paid for by the Judicial Council. Duties and Performance of the Laboratory Attend pre-construction meetings. Review shop drawings and submittals from construction contractors. Provide materials testing and special inspections of work in progress to ensure compliance with State and local building codes, architect's plans and specifications, and the requirements of the Judicial Council. The Laboratory shall also notify the Project Inspector as to the disposition of materials noted on laboratory testing, and/or special inspection, reports as not conforming to the Judicial Council approved documents. Special Inspections Special inspection by inspectors specially approved by Judicial Council may be required on certain types of construction work as described in the approved construction documents. Judicial Council may require Special Inspectors for types of construction in addition to those listed in Chapter 17 of Title 24, Part 2 if found necessary because of the special use of materials or methods of construction. Judicial Council may require Special Inspectors for any off-site fabrication procedures that preclude the complete inspection of the work after assembly. Special Inspectors shall be in the direct employ of the testing laboratory, and if not, subcontractors must be specifically approved by Judicial Council. Special Inspectors may be required to be approved by Judicial Council for each individual project prior to performing inspections. Approval of a Special Inspector’s resume and certifications shall be made on a case by case basis. A Special Inspector shall have had at least three years’ experience in construction work or inspection responsibilities on one or more projects similar to the project for which the inspector is applying, shall ...
SPECIAL INSPECTION AND TESTING. Inspection of Fabricators (OSSC1704.2.5) Steel Construction (OSSC 1705.2) Concrete Construction (OSSC 1705.3) Masonry Construction (OSSC 1705.4) Wood Construction (OSSC 1705.5) Soils (OSSC 1705.6)
SPECIAL INSPECTION AND TESTING. (To be filled in by plans examiner) The following inspections are required by the design professional in-charge and/or the building official:  Inspection of Fabricators  Cast-in-Place Deep Foundations  Steel Construction  Helical Pile Foundations  Concrete Construct  Sprayed Fire-Resistant Materials  Masonry Construction  Mastic & Intumescent Fire-Resistant Coating  Wood Construction  EIFS Installation  Soils  Fire-Resistant Penetrations and Joints  Radon MitigationSmoke Control  Post-Installed Anchors  Driven Deep Foundations  Others:
SPECIAL INSPECTION AND TESTING. (To be completed by plans examiner) The following inspections have been indicated within the program statement prepared by the design professional in responsible charge: Inspection of Fabricators (OSSC 1705.2) Steel Construction (OSSC 1705.2) Concrete Construction (OSSC 1705.3) Masonry Construction (OSSC 1705.4) Wood Construction (OSSC 1705.5) Soils (OSSC 1705.6) Radon Mitigation (OSSC 1705.18) Post-Installed Anchors (OSSC 1705.1.1(3)) Cast-in-Place Deep Foundations [Pier Foundation] (OSSC 1705.8) Helical Pile Foundations (OSSC 1705.9) Sprayed Fire-Resistant Materials (OSSC 1705.13) Mastic & Intumescent Fire-Resistant Coating (OSSC 1705.14) EIFS (OSSC 1705.15) Fire-Resistant Penetrations and Joints (OSSC 1705.16) Smoke Control (OSSC 1705.17) Driven Deep Foundations [Pile Foundation] (OSSC 1705.7) In accordance with OSSC Section 1705.1.1, the building official has determined that the following Special Case inspections are required:
AutoNDA by SimpleDocs
SPECIAL INSPECTION AND TESTING. The following special inspections, material testing and structural observations shall be performed according to IBC, Chapter 17 and the WABO Special Inspection Program. [X] Concrete - During the taking of test specimens and placing of reinforced concrete. (When the design compressive strength of concrete exceeds 2,500 psi) [ X] Bolts Installed in Concrete - Prior to and during the placement of concrete around bolts when stress increases permitted by Footnote 5 of Table 19-D or Section 1923 are utilized. [ ] Special Moment-Resisting Concrete Frame – For moment frames resisting design seismic load in structures within Seismic Zones C, D1, D2.

Related to SPECIAL INSPECTION AND TESTING

  • Inspection and Testing Each Constructing Entity shall cause inspection and testing of the Interconnection Facilities that it constructs in accordance with the provisions of this section. The Construction Parties acknowledge and agree that inspection and testing of facilities may be undertaken as facilities are completed and need not await completion of all of the facilities that a Constructing Entity is building.

  • Inspection and Tests 3.8.1 The Procuring entity or its representative shall have the right to inspect and/or to test the goods to confirm their conformity to the Contract specifications. The Procuring entity shall notify the tenderer in writing in a timely manner, of the identity of any representatives retained for these purposes.

  • Inspections and Tests 26.1 The Supplier shall at its own expense and at no cost to the Procuring Entity carry out all such tests and/or inspections of the Goods and Related Services as are specified in the SCC.

  • Inspection/Testing All Products sold pursuant to this Agreement will be subject to inspection/testing by or at the direction of H- GAC and/or the ordering Customer, either at the delivery destination or the place of manufacture. In the event a Product fails to meet or exceed all requirements of this Agreement, and unless otherwise agreed in advance, the cost of any inspection and/or testing, will be the responsibility of the Contractor.

  • Equipment Testing and Inspection 2.1.1 The Interconnection Customer shall test and inspect its Small Generating Facility and Interconnection Facilities prior to interconnection. The Interconnection Customer shall notify the NYISO and the Connecting Transmission Owner of such activities no fewer than five Business Days (or as may be agreed to by the Parties) prior to such testing and inspection. Testing and inspection shall occur on a Business Day. The Connecting Transmission Owner may, at its own expense, send qualified personnel to the Small Generating Facility site to inspect the interconnection and observe the testing. The Interconnection Customer shall provide the NYISO and Connecting Transmission Owner a written test report when such testing and inspection is completed. The Small Generating Facility may not commence parallel operations if the NYISO, in consultation with the Connecting Transmission Owner, finds that the Small Generating Facility has not been installed as agreed upon or may not be operated in a safe and reliable manner.

Time is Money Join Law Insider Premium to draft better contracts faster.