Power Factor Correction Charge Sample Clauses

Power Factor Correction Charge. KMEA shall provide adequate reactive compensation for KMEA’s Network Load to maintain at all times the load power factor at each of the delivery points shown in Appendix 2 between .95 lagging and .98 leading. KMEA conditions that result in excessive reactive flows will be corrected as soon as practical. KMEA shall compensate Mid-Kansas for excessive reactive flows at a rate consistent with SPP market practices. The Parties shall maintain the system voltages on their respective side of the Receipt Point in accordance with Good Utility Practice.
AutoNDA by SimpleDocs
Power Factor Correction Charge. Reserved
Power Factor Correction Charge. 8.78 Redispatch Charge Redispatch charges shall be in accordance with Section 33.3 of the Tariff. For request 1140120 and request 1161506, the Emporia Energy Center resource, provide generation redispatch power in the specified amounts necessary to alleviate loadings on the facilities listed in Attachment A prior to the completion of the planned Transmission Owner reliability network upgrades or new construction associated with each limiting facility. The specified amounts and constraining facilities for which redispatch will be required are also defined in Attachment A. The Network Customer agrees to provide at least one of the potential Westar redispatch pairs listed in Table 6 of the posted 2006-AG3-AFS-6 study, and the Transmission Provider agrees that such redispatch will satisfy the redispatch obligation. Such redispatch obligations shall be arranged in accordance with Attachment K of the Tariff and shall occur in advance of curtailment of other firm reservations impacting these constraints. Network Customer shall bear the cost of such redispatch. The interim network integration transmission service shall remain in place until the network upgrades are completed. For request and resource (denoted in table below), provide generation redispatch power in the specified amounts necessary to alleviate loading on the facilities listed in Attachment A prior to completion of Service, Reliability, and Construction Pending upgrades. The Network Customer agrees to provide at least one of the potential WR redispatch pairs listed in Table 6 of the final posting of study (denoted in table below) , and the Transmission Provider agrees that such redispatch will satisfy the redispatch obligation. OASIS Request Resource Aggregate Study 73315407 Central Plains Wind 2007-AG2 73447931 Xxxxxxxx Xxx Xxxx 0000-XX0 73447934 Flat Ridge Wind 2007-AG3 1457049 Xxxxxxx Energy Center 2008-AGP1 In the absence of implementation of interim redispatch as requested by the Transmission Provider for Network Customer transactions resulting in overloads on limiting facilities, the Transmission Provider shall curtail the customers schedule. Such redispatch obligations shall be arranged in accordance with Attachment K of the Tariff and shall occur in advance of curtailment of other firm reservations impacting these constraints. Network Customer shall bear the cost of such redispatch. The interim redispatch service shall remain in place until the network upgrades are completed.
Power Factor Correction Charge. KPP shall provide adequate reactive compensation for KPP’s Network Load to maintain at all times the load power factor at each of the delivery points shown in Appendix 2 between .95 lagging and .98 leading. KPP conditions that result in excessive reactive flows will be corrected as soon as practical. KPP shall compensate Local Delivery Provider for excessive reactive flows at a rate consistent with SPP market practices. The Parties shall maintain the system voltages on their respective side of the Receipt Point in accordance with Good Utility Practice.
Power Factor Correction Charge 

Related to Power Factor Correction Charge

  • Power Factor Requirement Consistent with Section 4.7 of Appendix 2 to this ISA, the power factor requirement is as follows: The Generation Interconnection Customer shall design its non-synchronous Customer Facility with the ability to maintain a power factor of at least 0.95 leading to 0.95 lagging measured at the high-side of the facility substation transformers.

  • Power Factor The Power Producer shall maintain the Power Factor as per the prevailing GERC regulations and as may be stipulated / specified by GETCO from time to time. The Power Producer shall provide suitable protection devices, so that the Electric Generators could be isolated automatically when grid supply fails. Connectivity criteria like short circuit level (for switchgear), neutral Grounding, fault clearance time, current unbalance (including negative and zero sequence currents), limit of harmonics etc. shall be as per Grid Code.

  • Power Factor Design Criteria (Reactive Power A wind generating plant shall maintain a power factor within the range of 0.95 leading to 0.95 lagging, measured at the Point of Interconnection as defined in this LGIA, if the ISO’s System Reliability Impact Study shows that such a requirement is necessary to ensure safety or reliability. The power factor range standards can be met using, for example without limitation, power electronics designed to supply this level of reactive capability (taking into account any limitations due to voltage level, real power output, etc.) or fixed and switched capacitors if agreed to by the Connecting Transmission Owner for the Transmission District to which the wind generating plant will be interconnected, or a combination of the two. The Developer shall not disable power factor equipment while the wind plant is in operation. Wind plants shall also be able to provide sufficient dynamic voltage support in lieu of the power system stabilizer and automatic voltage regulation at the generator excitation system if the System Reliability Impact Study shows this to be required for system safety or reliability.

  • Power Factor Design Criteria Developer shall design the Large Generating Facility to maintain an effective power delivery at demonstrated maximum net capability at the Point of Interconnection at a power factor within the range established by the Connecting Transmission Owner on a comparable basis, until NYISO has established different requirements that apply to all generators in the New York Control Area on a comparable basis. The Developer shall design and maintain the plant auxiliary systems to operate safely throughout the entire real and reactive power design range. The Connecting Transmission Owner shall not unreasonably restrict or condition the reactive power production or absorption of the Large Generating Facility in accordance with Good Utility Practice.

  • Meter Testing Company shall provide at least twenty-four (24) hours' notice to Seller prior to any test it may perform on the revenue meters or metering equipment. Seller shall have the right to have a representative present during each such test. Seller may request, and Company shall perform, if requested, tests in addition to the every fifth-year test and Seller shall pay the cost of such tests. Company may, in its sole discretion, perform tests in addition to the fifth year test and Company shall pay the cost of such tests. If any of the revenue meters or metering equipment is found to be inaccurate at any time, as determined by testing in accordance with this Section 10.2 (Meter Testing), Company shall promptly cause such equipment to be made accurate, and the period of inaccuracy, as well as an estimate for correct meter readings, shall be determined in accordance with Section 10.3 (Corrections).

  • Disaster Recovery PFPC shall enter into and shall maintain in effect with appropriate parties one or more agreements making reasonable provisions for emergency use of electronic data processing equipment to the extent appropriate equipment is available. In the event of equipment failures, PFPC shall, at no additional expense to the Fund, take reasonable steps to minimize service interruptions. PFPC shall have no liability with respect to the loss of data or service interruptions caused by equipment failure, provided such loss or interruption is not caused by PFPC's own willful misfeasance, bad faith, gross negligence or reckless disregard of its duties or obligations under this Agreement.

  • Voice Grade Unbundled Copper Sub-Loop Unbundled Sub-Loop Distribution – Intrabuilding Network Cable (aka riser cable)

  • Unbundled Voice Xxxx - XX0 (XXX-XX0). Loops are 2-wire loop start circuits, will be non-designed, and will not have remote access test points. OC will be offered as a chargeable option on XX0 Xxxxx when reuse of existing facilities has been requested by NewPhone, however, OC is always required on UCLs that involve the reuse of facilities that are currently providing service. NewPhone may also order OC-TS when a specified conversion time is requested. OC-TS is a chargeable option for any coordinated order and is billed in addition to the OC charge. An Engineering Information (EI) document can be ordered as a chargeable option. The EI document provides Loop Make-Up information which is similar to the information normally provided in a Design Layout Record (DLR). Upon issuance of a non-coordinated order in the service order system, XX0 Xxxxx will be activated on the due date in the same manner and time frames that BellSouth normally activates POTS-type Loops for its customers.

  • Switching System Hierarchy and Trunking Requirements For purposes of routing ECI traffic to Verizon, the subtending arrangements between Verizon Tandem Switches and Verizon End Office Switches shall be the same as the Tandem/End Office subtending arrangements Verizon maintains for the routing of its own or other carriers’ traffic (i.e., traffic will be routed to the appropriate Verizon Tandem subtended by the terminating End Office serving the Verizon Customer). For purposes of routing Verizon traffic to ECI, the subtending arrangements between ECI Tandem Switches and ECI End Office Switches shall be the same as the Tandem/End Office subtending arrangements that ECI maintains for the routing of its own or other carriers’ traffic.

  • Loop Provisioning Involving Integrated Digital Loop Carriers 2.6.1 Where InterGlobe has requested an Unbundled Loop and BellSouth uses IDLC systems to provide the local service to the End User and BellSouth has a suitable alternate facility available, BellSouth will make such alternative facilities available to InterGlobe. If a suitable alternative facility is not available, then to the extent it is technically feasible, BellSouth will implement one of the following alternative arrangements for InterGlobe (e.g. hairpinning):

Time is Money Join Law Insider Premium to draft better contracts faster.