Inundation Frequency Sample Clauses

Inundation Frequency. We estimated the magnitude of flows that inundated the alluvial deposits by surveying the topography of the Holocene alluvial valley along 78 cross sections in four locations (Table 3-1, Figure 3-2) during July and August 2005. The topography in the main channel of the Snake River was estimated with a digital depth sounder. Depth measurements were recorded at regular intervals across the channel and overlapped with at least two land-based survey measurements. We used the cross section data to develop one-dimensional flow models in HEC- RAS, a modeling program developed by the U.S. Army Corps of Engineers. We estimated the overbank roughness coefficient for all cross sections to be 0.08, a typical value for floodplains covered by grasses, bushes, and fallen and standing trees (Chow, 1959), such as is found along much of the Snake River alluvial valley. The stages of the modeled flows often did not precisely match those measured in the field during the specified flow; thus, we calibrated the flows at each cross section by changing the roughness coefficient of the channel until the stages of the modeled flows best matched those of the measured flows. We calibrated the flow models using water surface elevation data surveyed at each cross section during the 2005 dam-released flood, as this flood was closer in magnitude to the floods necessary to inundate the alluvial deposits than the late summer flows: the magnitude of the 2005 flows we surveyed ranged from 59 m3/s to 171 m3/s in Segment 3 (Table 3-2); the magnitudes of flows we modeled ranged from 213 m3/s to 889 m3/s in Segment 3. With the models calibrated to the 2005 peak flows, roughness coefficient values ranged from 0.015 to 0.05 in Segment 1, 0.02 to 0.048 in Segment 2, 0.022 to 0.05 in Segment 3, and 0.017 to 0.068 in Segment 4 (Table 3-3). Despite these adjustments to the roughness coefficient values, slight differences between modeled and measured water surface elevations for the 2005 peak flows remained. The greatest difference between measured and modeled water surface elevation was 0.11 m though the mean difference was less than 0.05 m for each reach (Table 3-4). All differences in stage were less than 7% of the maximum water depth along the cross section. After calibrating the models, we estimated the water surface elevation for up to 16 discharges at the upstream and downstream cross sections based on survey data and stage-discharge rating relationships, developed within HEC-RAS or from USGS ga...
AutoNDA by SimpleDocs

Related to Inundation Frequency

  • Reporting Frequency During any period of time when you are subject to the requirement in paragraph 1 of this award term and condition, you must report proceedings information through XXX for the most recent five year period, either to report new information about any proceeding(s) that you have not reported previously or affirm that there is no new information to report. Recipients that have Federal contract, grant, and cooperative agreement awards with a cumulative total value greater than $10,000,000 must disclose semiannually any information about the criminal, civil, and administrative proceedings.

  • Payment Frequency As of the Cutoff Date and as shown on the books of CNHCA: (A) Receivables having an aggregate Statistical Contract Value equal to 76.22% of the Aggregate Statistical Contract Value had annual scheduled payments, (B) Receivables having an aggregate Statistical Contract Value equal to 2.94% of the Aggregate Statistical Contract Value had semi-annual scheduled payments, (C) Receivables having an aggregate Statistical Contract Value equal to 0.82% of the Aggregate Statistical Contract Value had quarterly scheduled payments, (D) Receivables having an aggregate Statistical Contract Value equal to 16.40% of the Aggregate Statistical Contract Value had monthly scheduled payments, and (E) Receivables having an aggregate Statistical Contract Value equal to 3.62% of the Aggregate Statistical Contract Value had irregularly scheduled payments.

  • Reactive Power and Primary Frequency Response 9.6.1 Power Factor Design Criteria

  • Primary Frequency Response Developer shall ensure the primary frequency response capability of its Large Generating Facility by installing, maintaining, and operating a functioning governor or equivalent controls. The term “functioning governor or equivalent controls” as used herein shall mean the required hardware and/or software that provides frequency responsive real power control with the ability to sense changes in system frequency and autonomously adjust the Large Generating Facility’s real power output in accordance with the droop and deadband parameters and in the direction needed to correct frequency deviations. Developer is required to install a governor or equivalent controls with the capability of operating: (1) with a maximum 5 percent droop ± 0.036 Hz deadband; or (2) in accordance with the relevant droop, deadband, and timely and sustained response settings from an approved Applicable Reliability Standard providing for equivalent or more stringent parameters. The droop characteristic shall be: (1) based on the nameplate capacity of the Large Generating Facility, and shall be linear in the range of frequencies between 59 and 61 Hz that are outside of the deadband parameter; or (2) based on an approved Applicable Reliability Standard providing for an equivalent or more stringent parameter. The deadband parameter shall be: the range of frequencies above and below nominal (60 Hz) in which the governor or equivalent controls is not expected to adjust the Large Generating Facility’s real power output in response to frequency deviations. The deadband shall be implemented: (1) without a step to the droop curve, that is, once the frequency deviation exceeds the deadband parameter, the expected change in the Large Generating Facility’s real power output in response to frequency deviations shall start from zero and then increase (for under-frequency deviations) or decrease (for over-frequency deviations) linearly in proportion to the magnitude of the frequency deviation; or (2) in accordance with an approved Applicable Reliability Standard providing for an equivalent or more stringent parameter. Developer shall notify NYISO that the primary frequency response capability of the Large Generating Facility has been tested and confirmed during commissioning. Once Developer has synchronized the Large Generating Facility with the New York State Transmission System, Developer shall operate the Large Generating Facility consistent with the provisions specified in Articles 9.5.5.1 and 9.5.5.2 of this Agreement. The primary frequency response requirements contained herein shall apply to both synchronous and non-synchronous Large Generating Facilities.

  • Procurement from UN Agencies Goods estimated to cost less than $100,000 equivalent per contract may be procured directly from Inter-Agency Procurement Services Office (IAPSO) in accordance with the provisions of paragraphs 3.1 and 3.9 of the Procurement Guidelines.

  • Non-Synchronous Generation The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the high-side of the generator substation at a power factor within the range of 0.95 leading to 0.95 lagging, unless the NYISO or the Transmission Owner in whose Transmission District the Small Generating Facility interconnects has established a different power factor range that applies to all similarly situated non-synchronous generators in the control area or Transmission District (as applicable) on a comparable basis, in accordance with Good Utility Practice. This power factor range standard shall be dynamic and can be met using, for example, power electronics designed to supply this level of reactive capability (taking into account any limitations due to voltage level, real power output, etc.) or fixed and switched capacitors, or a combination of the two. This requirement shall only apply to newly interconnecting non-synchronous generators that have not yet executed a Facilities Study Agreement as of September 21, 2016.

  • Nuclear Hazard This Exclusion 7. pertains to Nuclear Hazard to the extent set forth in M. Nuclear Hazard Clause under Section I – Conditions.

  • Low Census Low census is defined as a decline in patient care requirements resulting in a temporary staff decrease. During periods of low census, the Employer will assign low census to nurses in the following order:

  • PAYMENT FROM OUTSIDE AGENCIES CONTRACTOR shall notify LEA when Medi-Cal or any other agency is billed for the costs associated with the provision of special education and/or related services covered by this Master Contract or the ISA to LEA pupils. Upon request, CONTRACTOR shall provide to LEA any and all documentation regarding reports, billing, and/or payment by Medi-Cal or any other agency for the costs associated with the provision of special education and/or related services covered by this Master Contract or ISA to LEA pupils.

  • Meeting Frequency SICM shall be held monthly unless otherwise agreed upon by all Parties. Meeting dates shall be determined by NCDEQ after consultation with the Parties. The meeting shall consist of updates and other pertinent information provided by each Party.

Time is Money Join Law Insider Premium to draft better contracts faster.