Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C of this LGIA that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth in Sections 9.6.4, 9.6.4.1, 9.6.4.2, and 9.6.4.3 of this LGIA. Appendix C shall specify whether the operating range is static or dynamic, and shall consider: (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C must establish how frequently the operating range will be reevaluated and the factors that may be considered during its reevaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section 9.6.4.2 of this LGIA when it is online and dispatched to inject electricity to the CAISO Controlled Grid and/or receive electricity from the Participating TO’s Transmission System or the CAISO Controlled Grid. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid and/or dispatched to receive electricity from the Participating TO’s Transmission system or the CAISO Controlled Grid. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-frequency deviations) or decrease (for under-frequency deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 20 contracts

Samples: Agreement, Large Generator Interconnection Agreement, Large Generator Interconnection Agreement

AutoNDA by SimpleDocs

Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C of this LGIA that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth in Sections 9.6.4, 9.6.4.1, 9.6.4.2, 9.6.4.2 and 9.6.4.3 of this LGIAGIA. Appendix C shall specify whether the operating range is static or dynamic, and shall consider: consider (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO Transmission Provider and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C must establish how frequently the operating range will be reevaluated and the factors that may be considered during its reevaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section 9.6.4.2 of this LGIA GIA when it is online and dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or receive electricity from the Participating TO’s Transmission System or the CAISO Controlled GridSystem. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or dispatched to receive electricity from the Participating TO’s Transmission system or the CAISO Controlled GridSystem. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-frequency deviations) or decrease (for under-frequency deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 17 contracts

Samples: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement

Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C Attachment 5 of this LGIA SGIA that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth in Sections 9.6.41.8.3, 9.6.4.11.8.3.1, 9.6.4.21.8.3.2, and 9.6.4.3 1.8.3.3 of this LGIASGIA. Appendix C Attachment 5 shall specify whether the operating range is static or dynamic, and shall consider: (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C Attachment 5 must establish how frequently the operating range will be reevaluated and the factors that may be considered during its reevaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section 9.6.4.2 1.8.3.2 of this LGIA SGIA when it is online and dispatched to inject electricity to the CAISO Controlled Grid and/or receive electricity from the Participating TO’s Transmission System or the CAISO Controlled Grid. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid and/or dispatched to receive electricity from the Participating TO’s Transmission system System or the CAISO Controlled Grid. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-frequency deviations) or decrease (for under-frequency deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 7 contracts

Samples: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement

Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C of this LGIA that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth in Sections 9.6.4, 9.6.4.1, 9.6.4.2, and 9.6.4.3 of this LGIA. Appendix C shall specify whether the operating range is static or dynamic, and shall consider: consider (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C must establish how frequently the operating range will be reevaluated and the factors that may be considered during its reevaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section 9.6.4.2 of this LGIA when it is online and dispatched to inject electricity to the CAISO Controlled Grid and/or receive electricity from the Participating TO’s Transmission System or the CAISO Controlled Grid. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid and/or dispatched to receive electricity from the Participating TO’s Transmission system or the CAISO Controlled Grid. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-frequency deviations) or decrease (for under-frequency deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 7 contracts

Samples: Large Generator Interconnection Agreement, Large Generator Interconnection Agreement, Large Generator Interconnection Agreement

Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C Attachment 5 of this LGIA its SGIA that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth in Sections 9.6.41.8.4, 9.6.4.11.8.4.1, 9.6.4.2, 1.8.4.2 and 9.6.4.3 1.8.4.3 of this LGIAAgreement. Appendix C Attachment 5 shall specify whether the operating range is static or dynamic, and shall consider: (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO Transmission Provider and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C Attachment 5 must establish how frequently the operating range will be reevaluated and the factors that may be considered during its reevaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section 9.6.4.2 1.8.4.2 of this LGIA Agreement when it is online and dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or receive electricity from the Participating TO’s Transmission System or the CAISO Controlled GridSystem. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or dispatched to receive electricity from the Participating TO’s Transmission system or the CAISO Controlled GridSystem. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-frequency deviations) or decrease (for under-frequency deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 4 contracts

Samples: Small Generator Interconnection Agreement, Small Generator Interconnection Agreement, Small Generator Interconnection Agreement

Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C Attachment 5 of this LGIA SGIA that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth in Sections 9.6.41.8.3, 9.6.4.11.8.3.1, 9.6.4.21.8.3.2, and 9.6.4.3 1.8.3.3 of this LGIASGIA. Appendix C Attachment 5 shall specify whether the operating range is static or dynamic, and shall consider: (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C Attachment 5 must establish how frequently the operating range will be reevaluated and the factors that may be considered during its reevaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section 9.6.4.2 1.8.3.2 of this LGIA SGIA when it is online and dispatched to inject electricity to the CAISO Controlled Grid and/or receive electricity from the Participating TO’s Transmission System or the CAISO Controlled Grid. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid and/or dispatched to receive electricity from the Participating TO’s Transmission system System or the CAISO Controlled Grid. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-over- frequency deviations) or decrease (for under-frequency deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 4 contracts

Samples: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement

Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C Attachment 5 of this LGIA its GIA that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth in Sections 9.6.4articles 1.8.4, 9.6.4.11.8.4.1, 9.6.4.2, 1.8.4.2 and 9.6.4.3 1.8.4.3 of this LGIAAgreement. Appendix C Attachment 5 shall specify whether the operating range is static or dynamic, and shall consider: (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO Distribution Provider and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C Attachment 5 must establish how frequently the operating range will be reevaluated and the factors that may be considered during its reevaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section 9.6.4.2 article 1.8.4.2 of this LGIA Agreement when it is online and dispatched to inject electricity to the CAISO Controlled Grid Distribution System and/or receive electricity from the Participating TO’s Transmission System or the CAISO Controlled GridDistribution System. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid Distribution System and/or dispatched to receive electricity from the Participating TO’s Transmission system or the CAISO Controlled GridDistribution System. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-frequency deviations) or decrease (for under-frequency deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 3 contracts

Samples: Service Agreement, Service Agreement, Generator Interconnection Agreement

Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C of this LGIA its GIA that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth in Sections 9.6.4, 9.6.4.1, 9.6.4.2, 9.6.4.2 and 9.6.4.3 of this LGIAAgreement. Appendix C shall specify whether the operating range is static or dynamic, and shall consider: consider (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO Transmission Provider and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C must establish how frequently the operating range will be reevaluated and the factors that may be considered during its reevaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section 9.6.4.2 of this LGIA Agreement when it is online and dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or receive electricity from the Participating TO’s Transmission System or the CAISO Controlled GridSystem. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or dispatched to receive electricity from the Participating TO’s Transmission system or the CAISO Controlled GridSystem. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-frequency deviations) or decrease (for under-frequency deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 2 contracts

Samples: Generator Interconnection Agreement, Interim Generator Interconnection Agreement

Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C of this LGIA that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth in Sections 9.6.4, 9.6.4.1, 9.6.4.2, 9.6.4.2 and 9.6.4.3 of this LGIAGIA. Appendix C shall specify whether the operating range is static or dynamic, and shall consider: consider (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational FERC Electric Tariff Generator Interconnection Agreement (GIA) ATTACHMENTS 92.0.0 limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO Transmission Provider and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C must establish how frequently the operating range will be reevaluated and the factors that may be considered during its reevaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section 9.6.4.2 of this LGIA GIA when it is online and dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or receive electricity from the Participating TO’s Transmission System or the CAISO Controlled GridSystem. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or dispatched to receive electricity from the Participating TO’s Transmission system or the CAISO Controlled GridSystem. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-frequency deviations) or decrease (for under-frequency deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 1 contract

Samples: Generator Interconnection Agreement

Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C of this its LGIA that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth in Sections Articles 9.6.4, 9.6.4.1, 9.6.4.2, 9.6.4.2 and 9.6.4.3 of this LGIAAgreement. Appendix C shall specify whether the operating range is static or dynamic, and shall consider: consider (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO Transmission Provider and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C must establish how frequently the operating range will be reevaluated and the factors that may be considered during its reevaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section Article 9.6.4.2 of this LGIA Agreement when it is online and dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or receive electricity from the Participating TO’s Transmission System or the CAISO Controlled GridSystem. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or dispatched to receive electricity from the Participating TO’s Transmission system or the CAISO Controlled GridSystem. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-frequency deviations) or decrease (for under-frequency deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 1 contract

Samples: Agreement

Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C of this LGIA that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth in Sections 9.6.4, 9.6.4.1, 9.6.4.2, and 9.6.4.3 of this LGIA. Appendix C shall specify whether the operating range is static or dynamic, and shall consider: (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C must establish how frequently the operating range will be reevaluated and the factors that may be considered during its reevaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section 9.6.4.2 of this LGIA when it is online and dispatched to inject electricity to the CAISO Controlled Grid and/or receive electricity from the Interconnecting Participating TO’s Transmission System or the CAISO Controlled Grid. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid and/or dispatched to receive electricity from the Interconnecting Participating TO’s Transmission system or the CAISO Controlled Grid. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-frequency deviations) or decrease (for under-frequency deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 1 contract

Samples: Large Generator Interconnection Agreement

Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C of this LGIA its GIA that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth in Sections 9.6.4, 9.6.4.1, 9.6.4.2, 9.6.4.2 and 9.6.4.3 of this LGIAAgreement. Appendix C shall specify whether the operating range is static or dynamic, and shall consider: consider (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO Transmission Provider and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C must establish how frequently the operating range will be reevaluated and the factors that may be considered during its reevaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section 9.6.4.2 of this LGIA Agreement when it is online and dispatched to inject injec t electricity to the CAISO Controlled Grid Transmission System and/or receive electricity from the Participating TO’s Transmission System or the CAISO Controlled GridSystem. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or dispatched to receive electricity from the Participating TO’s Transmission system or the CAISO Controlled GridSystem. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-frequency deviations) or decrease (for under-frequency frequenc y deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 1 contract

Samples: Generator Interconnection Agreement

AutoNDA by SimpleDocs

Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C of this its LGIA that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth in Sections 9.6.4, 9.6.4.1, 9.6.4.2, 9.6.4.2 and 9.6.4.3 of this LGIAAgreement. Appendix C shall specify whether the operating range is static or dynamic, and shall consider: consider (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO Transmission Provider and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C must establish how frequently the operating range will be reevaluated and the factors that may be considered during its reevaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section 9.6.4.2 of this LGIA Agreement when it is online and dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or receive electricity from the Participating TO’s Transmission System or the CAISO Controlled GridSystem. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or dispatched to receive electricity from the Participating TO’s Transmission system or the CAISO Controlled GridSystem. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-frequency deviations) or decrease (for under-frequency deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 1 contract

Samples: Revision History*

Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C of this LGIA its JAGITS that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth in Sections 9.6.4, 9.6.4.1, 9.6.4.2, 9.6.4.2 and 9.6.4.3 of this LGIAAgreement. Appendix C shall specify whether the operating range is static or dynamic, and shall consider: consider (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO JEA and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C must establish how frequently the operating range will be reevaluated and the factors that may be considered during its reevaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section 9.6.4.2 of this LGIA Agreement when it is online and dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or receive electricity from the Participating TO’s Transmission System or the CAISO Controlled GridSystem. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or dispatched to receive electricity from the Participating TO’s Transmission system or the CAISO Controlled GridSystem. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-frequency deviations) or decrease (for under-frequency deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 1 contract

Samples: www.oatioasis.com

Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C of this LGIA that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth LARGE GENERATOR INTERCONNECTION AGREEMENT in Sections 9.6.4, 9.6.4.1, 9.6.4.2, and 9.6.4.3 of this LGIA. Appendix C shall specify whether the operating range is static or dynamic, and shall consider: consider (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C must establish how frequently the operating range will be reevaluated and the factors that may be considered during its reevaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section 9.6.4.2 of this LGIA when it is online and dispatched to inject electricity to the CAISO Controlled Grid and/or receive electricity from the Participating TO’s Transmission System or the CAISO Controlled Grid. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid and/or dispatched to receive electricity from the Participating TO’s Transmission system or the CAISO Controlled Grid. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-frequency deviations) or decrease (for under-frequency deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 1 contract

Samples: Large Generator Interconnection Agreement

Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C Attachment 5 of this LGIA its SGIA that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth in Sections 9.6.4Articles 1.8.4, 9.6.4.11.8.4.1, 9.6.4.2, 1.8.4.2 and 9.6.4.3 1.8.4.3 of this LGIAAgreement. Appendix C Attachment 5 shall specify whether the operating range is static or dynamic, and shall consider: (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO Transmission Provider and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C Attachment 5 must establish how frequently the operating range will be reevaluated and the factors that may be considered during its reevaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section 9.6.4.2 Article 1.8.4.2 of this LGIA Agreement when it is online and dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or receive electricity from the Participating TO’s Transmission System or the CAISO Controlled GridSystem. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or dispatched to receive electricity from the Participating TO’s Transmission system or the CAISO Controlled GridSystem. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-frequency deviations) or decrease (for under-frequency deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 1 contract

Samples: Small Generator Interconnection Agreement

Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C of this LGIA that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth in Sections Articles 9.6.4, 9.6.4.1, 9.6.4.2, and 9.6.4.3 of this LGIA. Appendix C shall specify whether the operating range is static or dynamic, and shall consider: (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C must establish how frequently the operating range will be reevaluated and the factors that may be considered during its reevaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section Article 9.6.4.2 of this LGIA when it is online and dispatched to inject electricity to the CAISO Controlled Grid and/or receive electricity from the Participating TO’s Transmission System or the CAISO Controlled Grid. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid and/or dispatched to receive electricity from the Participating TO’s Transmission system or the CAISO Controlled Grid. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-frequency deviations) or decrease (for under-frequency deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and DocuSign Envelope ID: 641570BA-608D-4F84-9EF7-D42DF0E7E18D deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 1 contract

Samples: Agreement

Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C of this its LGIA that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth in Sections Articles 9.6.4, 9.6.4.1, 9.6.4.2, and 9.6.4.3 of this LGIAAgreement. Appendix C shall specify whether the operating range is static or dynamic, and shall consider: consider (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO Transmission Provider and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C must establish how frequently the operating range will be reevaluated and the factors that may be considered during its reevaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section Article 9.6.4.2 of this LGIA Agreement when it is online and dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or receive electricity from the Participating TO’s Transmission System or the CAISO Controlled GridSystem. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or dispatched to receive electricity from the Participating TO’s Transmission system or the CAISO Controlled GridSystem. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-frequency deviations) or decrease (for under-under- frequency deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 1 contract

Samples: Large Generator Interconnection Agreement

Electric Storage Resources. Interconnection Customer interconnecting an electric storage resource shall establish an operating range in Appendix C A of this LGIA the SGIA that specifies a minimum state of charge and a maximum state of charge between which the electric storage resource will be required to provide primary frequency response consistent with the conditions set forth in Sections Articles 9.6.4, 9.6.4.1, 9.6.4.2, 9.6.4.1 and 9.6.4.3 9.6.4.2 of this LGIAAgreement. Appendix C A shall specify whether the operating range is static or dynamic, and shall consider: consider (1) the expected magnitude of frequency deviations in the interconnection; (2) the expected duration that system frequency will remain outside of the deadband parameter in the interconnection; (3) the expected incidence of frequency deviations outside of the deadband parameter in the interconnection; (4) the physical capabilities of the electric storage resource; (5) operational limitations of the electric storage resource due to manufacturer specifications; and (6) any other relevant factors agreed to by the CAISO Transmission Provider and Interconnection Customer, and in consultation with the relevant transmission owner or balancing authority as appropriate. If the operating range is dynamic, then Appendix C A must establish how frequently the operating range will be reevaluated re-evaluated and the factors that may be considered during its reevaluationre-evaluation. Interconnection Customer’s electric storage resource is required to provide timely and sustained primary frequency response consistent with Section Article 9.6.4.2 of this LGIA Agreement when it is online and dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or receive electricity from the Participating TO’s Transmission System or the CAISO Controlled GridSystem. This excludes circumstances when the electric storage resource is not dispatched to inject electricity to the CAISO Controlled Grid Transmission System and/or dispatched to receive electricity from the Participating TO’s Transmission system or the CAISO Controlled GridSystem. If Interconnection Customer’s electric storage resource is charging at the time of a frequency deviation outside of its deadband parameter, it is to increase (for over-over- frequency deviations) or decrease (for under-under- frequency deviations) the rate at which it is charging in accordance with its droop parameter. Interconnection Customer’s electric storage resource is not required to change from charging to discharging, or vice versa, unless the response necessitated by the droop and deadband settings requires it to do so and it is technically capable of making such a transition.

Appears in 1 contract

Samples: Interconnection Agreement