Revenue Metering. The Connecting Transmission Owner-owned revenue metering shall be located at the Sky High Solar Collector Substation and shall consist of: • three (3) combination current/potential transformers (“CT/PT”) units; and • one (1) ▇▇▇▇▇▇ + Gyr MaxSys Elite meter. (Note: The Company’s revenue metering CTs and VTs cannot be used to feed the Interconnection Customer’s check meter.)
Appears in 6 contracts
Sources: Interconnection Agreement, Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement
Revenue Metering. The Connecting Transmission Owner-Owner owned revenue metering shall be located at the Sky High ▇▇▇▇▇ Solar Collector Substation on the generator side of the 69kV breaker and shall consist of: • three (3) combination current/potential transformers voltage transformer (“CT/PTVT”) unitsunits (manufacturer and model shall be ABB/▇▇▇▇▇▇▇ KXM-350 high accuracy, or other Connecting Transmission Owner specified equivalent); and • one (1) ▇▇▇▇▇▇ + Gyr MaxSys Elite revenue meter. (Note: The CompanyConnecting Transmission Owner’s revenue metering CTs and VTs cannot be used to feed the Interconnection Customer’s check meter.)
Appears in 5 contracts
Sources: Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement
Revenue Metering. The Connecting Transmission Owner-owned revenue metering shall be located at the Sky High Solar Collector Substation and shall consist of: • three (3) combination current/potential transformers (“CT/PT”) units; and • one (1) ▇▇▇▇▇▇ + Gyr MaxSys Elite meter. (Note: The Company’s revenue metering CTs and VTs cannot be used to feed the Interconnection Customer’s check meter.)and
Appears in 1 contract