Receptacles. Convenience receptacles shall be limited to eight per circuit, with a circuit loading of 180 ▇▇▇▇▇ for each receptacle, unless specific conditions necessitate other requirements. Maximum spacing of receptacles along walls in office areas and maintenance shop shall not exceed 12 feet. Each office shall have a minimum of two receptacles. 120 V convenience receptacles shall be installed in operating areas at 70 foot intervals, on the basis of ▇▇-▇▇▇▇ ▇▇▇▇▇▇▇▇▇ ▇▇▇▇▇. Convenience receptacles shall be provided at each manway platform. Office and administration areas shall have a duplex receptacle, two wire, three pole, grounded type, rated 15 amperes, 125 volts ac. Welding outlet circuits shall consist of No. 4 AWG or larger conductors with circuit protective devices located in the low voltage motor control centers. Each circuit shall supply a maximum of three welding receptacles. Outlets shall be provided in the operating areas and shall be located at points that may require the greatest service. Outlets shall be located so that no point in that area requires a welding cable in excess of 125 feet. Welding receptacles shall be three wire, four pole, rated 60 amperes, 600 volts ac, three phase.