Common use of Keypad Clause in Contracts

Keypad. Two analog inputs, each capable of accepting a 0-20 mA, 4-20 mA, 0-10 V, 2-10 V signal. Input shall be isolated from ground, and programmable via the keypad for different uses. Analog inputs shall have a programmable filter to remove any oscillation of the reference signal. The filter shall be adjustable from 0.01-10 seconds. The analog input should be able to be inverted, so that minimum reference corresponds to maximum speed, and maximum reference corresponds to minimum speed. The minimum and maximum values (gain and offset) shall be adjustable within the range of 0-20 mA and 0-10 volts.

Appears in 3 contracts