Ventilation. LANDLORD shall provide a minimum of 20 cubic feet of outdoor fresh air per minute per person in the Leased Premises as outlined in Table 2 of ASHRAE (American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc.) Standard 62-1989. An air cleaning device shall be used in the ventilation system which filters the outdoor air and shall have a minimum filtration efficiency rating of 30 percent as measured by ASHRAE Standard 52-92 Atmospheric Dust Spot Efficiency Rating. If air filters are used, LANDLORD shall change the filters at least three (3) times per year, preferably in March, July and November, or more often as required. Where there is a secondary filtration system, such as buildings with heat pumps, the secondary filtration system shall have a minimum filtration efficiency rating of ten (10) percent as measured by ASHRAE Standard 52-92 Atmospheric Dust Spot Efficiency Rating. If air filters are used, LANDLORD shall change the filters at least two (2) times per year, or more often if required. LANDLORD shall remove and replace any building material with visible or detected evidence of water infiltration or mold growth. Restrooms: LANDLORD shall provide the Leased Premises with separate restroom facilities for both men and women. Such facilities shall either be situated within the Leased Premises or easily accessible thereto. LANDLORD warrants that said restrooms are in compliance with the Americans With Disabilities Act (the “ADA”) requirements.