Switchboards Sample Clauses

Switchboards. One (1) 3000A, three (3) 800A, and one (1) 400A.
AutoNDA by SimpleDocs
Switchboards. Tenant shall have the right to connect its electrical system to the Building’s main switchboards (MSB5 and MSB6). Tenant shall be solely responsible for the electrical usage costs incurred therewith. The maximum fuse of the switchboards is 800 AMPS each.
Switchboards. All boards shall be in accordance with the types as specified, be constructed according to the detail or type drawings and must be approved before installation. In all instances where provision is to be made on boards for supply authority’s main switch and/or metering equipment the Contractor must ensure that all requirements of the authorities concerned in this respect are met. Any construction, or standard type board proposed as an alternative to that specified, must have the prior approval of the department. All busbars, wiring, terminals, etc, are to be adequately insulated and all wiring is to enter the switchgear from the back of the board. The switchgear shall be mounted within the boards to give flush to the panel. Cable end boxes and other ancillary equipment must be provided where required. Clearly engraved labels are to be mounted on or below every switch. The wording of the labels in English is to be according the lay-out drawings or as directed by the Employer’s Representative and must be confirmed on site. Flush mounted boards to be installed with the top of board 1800mm above the finished floor level.
Switchboards. 4. Motor control centers.
Switchboards. The contractor will be responsible for plant and emergency repairs, periodical servicing and testing of 11kV and 400V switchboards. Circuit Breakers The contractor will be responsible for servicing, repairing and testing of 400V, 11kV circuit breakers. This will include periodic testing of the insulating oil, operating mechanism, trip units, oil leakages, functionality, etc.
Switchboards. The 415V switchboards shall be of the multi-unit type comprising circuit breakers, isolating switches and motor starters. Fused switches may be offered as an alternative to MCCB's. The switchboard as a whole shall be capable of sustaining, without damage, the electrical and mechanical stresses imposed by fault conditions in accordance with IEC 60439. The switchboards, and the individual components thereof, shall be `type tested' by a recognised short circuit testing authority in accordance with the above rating and copies of test Certificates proving this rating shall be submitted to Owner.

Related to Switchboards

  • Lighting A system of fixtures providing or controlling the light sources used on or near the airport or within the airport buildings. The field lighting includes all luminous signals, markers, floodlights, and illuminating devices used on or near the airport or to aid in the operation of aircraft landing at, taking off from, or taxiing on the airport surface.

  • Electrical Provide drawings for the following systems:

  • Switching All of the negotiated rates, terms and conditions set forth in this Section pertain to the provision of local and tandem switching.

  • Generators Temporary installation of generators, and permanent installation of generators that are placed inside existing non-residential buildings or that occupy an area under 50 square feet behind the building they serve.

  • SPRINKLER SYSTEM If there now is or shall be installed in the Building a "sprinkler system", and such system or any of its appliances shall be damaged or injured or not in proper working order by reason of any act or omission of Tenant, Tenant's agents, servants, employees, licensees or visitors, Tenant shall forthwith restore the same to good working condition at its own expense; and if the New York Board of Fire Underwriters or the New York Fire Insurance Rating Organization or any bureau, department or official of the state or city government, shall require or recommend that any changes, modifications, alterations or additional sprinkler heads or other equipment be made or supplied by reason of Tenant's business, or the location of the partitions, trade fixtures, or other contents of the Premises, Tenant shall, at Tenant's expense, promptly make and supply such changes, modifications, alterations, additional sprinkler heads or other equipment.

  • Elevators Landlord shall provide passenger elevator service during normal business hours to Tenant in common with Landlord and all other tenants. Landlord shall provide limited passenger service at other times, except in case of an emergency.

  • Plumbing fixtures and appliances shall be used only for the purposes for which designed, and no sweepings, rubbish, rags or other unsuitable material shall be thrown or deposited therein. Damage resulting to any such fixtures or appliances from misuse by a tenant or its agents, employees or invitees, shall be paid by such tenant.

  • Radios The Contractor or its employees shall not use any of the two-way radios or special telecommunications equipment under any circumstances. No exceptions will be made to this rule. Violation is grounds for immediate termination of this Contract, as well as punitive action.

  • Local Switching BellSouth shall provide non-discriminatory access to local circuit switching capability, and local tandem switching capability, on an unbundled basis, except as set forth below in Section 3.1.3 to Mpower for the provision of a telecommunications service. BellSouth shall provide non-discriminatory access to packet switching capability on an unbundled basis to Mpower for the provision of a telecommunications service only in the limited circumstance described below in Section 3.3.4.6.

  • Cameras j) Portable music player, headphones.

Time is Money Join Law Insider Premium to draft better contracts faster.