Common use of Reactive Power Clause in Contracts

Reactive Power. 1.8.1 The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range established by the Connecting Transmission Owner on a comparable basis, until NYISO has established different requirements that apply to all similarly situated generators in the New York Control Area on a comparable basis.

Appears in 61 contracts

Samples: Standard Small Generator Interconnection Agreement, Small Generator Interconnection Agreement, Standard Small Generator Interconnection Agreement

AutoNDA by SimpleDocs

Reactive Power. 1.8.1 The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range established by of 0.95 leading to 0.95 lagging, unless the Connecting Transmission Owner on a comparable basis, until NYISO Provider has established different requirements that apply to all similarly situated generators in the New York Control Area control area on a comparable basis. The requirements of this paragraph shall not apply to wind generators.

Appears in 35 contracts

Samples: Study Agreement, Small Generator Interconnection Agreement, Interconnection Agreement

Reactive Power. 1.8.1 The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point terminals of Interconnection each generating unit at a power factor within the range established by the Connecting Transmission Owner on a comparable basis, until NYISO has established different requirements that apply to all similarly situated generators in the New York Control Area on a comparable basis.of

Appears in 3 contracts

Samples: Small Generator Interconnection Agreement, Small Generator Interconnection Agreement, Small Generator Interconnection Agreement

Reactive Power. 1.8.1 1.7.1 The Interconnection Customer shall design its Small Generating Facility and operate the generating facility to maintain a composite power delivery at continuous rated power output at the Point point of Interconnection interconnection at a power factor within in accordance with the range established by the Connecting Transmission Owner on a comparable basis, until NYISO has established different requirements that apply to all similarly situated generators in the New York Control Area on a comparable basisHEA Generation Interconnection Procedure.

Appears in 2 contracts

Samples: Generation Interconnection Agreement, Interconnection Agreement

AutoNDA by SimpleDocs

Reactive Power. 1.8.1 The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range established of 0.95 leading to 0.95 lagging, unlessestablished by the Connecting Transmission Owner ProviderOwner on a comparable basis, until NYISO has established different requirements that apply to all similarly situated generators in the New control areaNew York Control Area on a comparable basis. The requirements of this paragraph shall not apply to wind generators.

Appears in 1 contract

Samples: Interconnection Agreement