Reactive Power Sample Clauses

Reactive Power. 1.8.1 The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the range established by the Connecting Transmission Owner on a comparable basis, until NYISO has established different requirements that apply to all similarly situated generators in the New York Control Area on a comparable basis.
AutoNDA by SimpleDocs
Reactive Power. 1.8.1 The Interconnection Customer shall design its Small Generating Facility to maintain a composite power delivery at continuous rated power output at the terminals of each generating unit at a power factor within the range of 0.95 leading to 0.90 lagging, unless the CAISO has established different requirements that apply to all similarly situated generators in the CAISO Balancing Authority Area on a comparable basis. The requirements of this paragraph shall not apply to wind generators and the requirements of Attachment 7 shall apply instead.
Reactive Power. The Interconnection Customer shall design its Small Generator Facility to maintain a composite power delivery at continuous rated power output at the Point of Interconnection at a power factor within the power factor range required by the EDC’s applicable tariff for a comparable load customer. EDC may also require the Interconnection Customer to follow a voltage or VAR schedule if such schedules are applicable to similarly situated generators in the control area on a comparable basis and have been approved by the Commission. The specific requirements for meeting a voltage or VAR schedule shall be clearly specified in Attachment 4. Under no circumstance shall these additional requirements for reactive power or voltage support exceed the normal operating capabilities of the Small Generator Facility.
Reactive Power. The Interconnection Customer shall design its Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Common Coupling at a power factor within the range of 0.95 leading to 0.95 lagging.
Reactive Power. 7.8.1 In order to maintain grid stability and prevent any excess drawal of reactive power, the SPV shall install capacitor banks or such other means capable of generating reactive power. The reactive power charges (including penalty to any governmental authority for excess reactive power drawn) and charges against power drawn from grid as per CERC / MERC regulations, shall be payable by the SPV as per provisions herein.
Reactive Power. 9.6.1 Power Factor Design Criteria ................................................................................... 9.6.2 Voltage Schedules....................................................................................................
AutoNDA by SimpleDocs
Reactive Power. 1.9.1 Interconnection customers with a distributed generation facility larger than or equal to 1 MVA shall design their distributed generation facilities to maintain a power factor at the point of interconnection between .95 lagging and .95 leading at all times. Interconnection customers with a distributed generation facility smaller than 1 MVA shall design their distributed generation facility to maintain a power factor at the point of interconnection between .90 lagging and .90 leading at all times.
Reactive Power. Both the Authority and the Company shall supply or absorb reactive power as may be desirable, insofar as in their judgment they are able to do so without adverse effects. The Authority will supply reactive power as required to assure adequate voltage at the point of delivery. The Authority will not be obligated to supply reactive power at the point of receipt in the Company’s system, but it may do so at extra charge, if requested.