Final Test Sample Clauses

Final Test. For a final test, operate the motor and/or pump under no load. Test the insulation resistance. Inspect the motor and/or pump for undue temperature, vibration and noise. Check the cooling fluid in submersible motors and/or pumps. Check for mechanical seal leaks, check for seal and thermal alarm operation. Correct any deficiency
AutoNDA by SimpleDocs
Final Test a) The final test (hereinafter, “Final Test”) consists of a test to be performed on each of the Product in order to verify if they are in compliance with the technical requirements included within the Order Confirmation.
Final Test a) a) After the development is by over pumping and surging is complete the, the well shall be tested for its performance, i.e. yield characteristics and efficiency. This shall be achieved by conducting a step draw down test – determining draw down at the end of the hour by pumping at 5 to 8 different rates of discharge near the rated discharge. Preferably, the test should be conducted in a single day and the time of running of Tubewell for each discharge shall be same say 1 - 2 hour. The data from the test can be used to determine the relative proportion of laminar and turbulent flow occurring, true efficiency and rated discharge of the well and working out the suitable parameter for the pump.
Final Test. YIELD RECONCILIATION. Supplier and Buyer shall perform a final test yield reconciliation to adjust test services pricing on a monthly basis. The actual yield will be compared with the financial standard yield. The yield variance will be calculated as the delta between the financial standard cost yield used for setting standards and the actual yield. Adjustments made to correct yield transactions should also be taken into consideration. A credit or debit memo will be issued from the Supplier to Buyer.

Related to Final Test

  • ACCEPTANCE TESTS 11.1 If the Contract provides acceptance tests for Goods and/or the result of Services after their completion and/or delivery to the Purchaser, the acceptance shall only be considered as definitive when such tests have demonstrated the compliance of the Goods and/or the result of the Services to the requirements in the Contract.

  • Performance Tests Contractor shall perform Performance Tests in accordance with Section 11.2 of the Agreement and Attachment S.

  • Performance Testing 7.2.1 The Design-Builder shall direct and supervise the tests and, if necessary, the retests of the Plant using Design-Builder’s supervisory personnel and the Air Emissions Tester shall conduct the air emissions test, in each case, in accordance with the testing procedures set forth in Exhibit A (the “Performance Tests”), to demonstrate, at a minimum, compliance with the Performance Guarantee Criteria. Owner is responsible for obtaining Air Emissions Tester and for ensuring Air Emissions Tester’s timely performance. Design-Builder shall cooperate with the Air Emissions Tester to facilitate performance of all air emissions tests. Design-Builder shall not be held responsible for the actions of Owner’s employees and third parties involved in the Performance Testing, including but not limited to Air Emissions Tester.

  • Acceptance Testing At the time of installation of a LIS trunk group, and at no additional charge, acceptance tests will be performed to ensure that the service is operational and meets the applicable technical parameters.

  • Stability Testing Patheon may be requested to conduct stability testing on the Products in accordance with the protocols set out in the Specifications for the separate fees and during the time periods set out in Schedule C to a Product Agreement. Patheon will not make any changes to these testing protocols without prior written approval from Client. If a confirmed stability test failure occurs, Patheon will notify Client within one Business Day, after which Patheon and Client will jointly determine the proceedings and methods to be undertaken to investigate the cause of the failure, including which party will bear the cost of the investigation. Patheon will not be liable for these costs unless it has failed to perform the Manufacturing Services in accordance with the Specifications, cGMPs, and Applicable Laws. Patheon will give Client ail stability test data and results at Client’s request.

  • Test The outer surface of the lamp lenses shall be subjected once or more than once to the action of the sand jet produced as described above. The jet shall be sprayed almost perpendicular to the surface to be tested. The deterioration shall be checked by means of one or more samples of glass placed as a reference near the lenses to be tested. The mixture shall be sprayed until the variation in the diffusion of light on the sample or samples measured by the method described in Appendix 2, is such that: Δ d = (T5 - T4) / T2 ≤ 0.0250 ± 0.0025 Several reference samples may be used to check that the whole surface to be tested has deteriorated homogeneously. Annex 6 - Appendix 4

  • Alcohol Testing Alcohol testing will be conducted by using an evidential breath testing device (EBT) approved by the National Highway Traffic Safety Administration. Non-EBT devices may be used for initial screening tests. A screening test will be conducted first. If the result is an alcohol concentration level of less than 0.02, the test is considered a negative test. If the alcohol concentration level is 0.02 or more, a second confirmation test will be conducted. Levels of .04 or greater on the confirmation test will be considered positive.

  • Random Testing Notwithstanding any provisions of the Collective Agreement or any special agreements appended thereto, section 4.6 of the Canadian Model will not be applied by agreement. If applied to a worker dispatched by the Union, it will be applied or deemed to be applied unilaterally by the Employer. The Union retains the right to grieve the legality of any imposition of random testing in accordance with the Grievance Procedure set out in this Collective Agreement.

Time is Money Join Law Insider Premium to draft better contracts faster.