Final Test Sample Clauses

Final Test a) The final test (hereinafter, “Final Test”) consists of a test to be performed on each of the Product in order to verify if they are in compliance with the technical requirements included within the Order Confirmation. b) The Final Test will be carried out at MEI’s facility no later than 15 (fifteen) days before the Delivery Date and the following procedure shall apply: (i) no later than 30 (thirty) days before the Delivery Date, Purchaser may request in writing to MEI to participate at the Final Test (hereinafter, “Participation Notice”). Within such written request, Purchaser shall also indicate to MEI a proposal date for the Final Test to be confirmed by ▇▇▇ in writing. (ii) no later than 5 (five) Business Days after the receipt of the Participation Notice, MEI shall have to confirm the Final Test date proposed by Purchaser or negotiate another Final Test date suitable for both Parties. c) The Parties hereby agree that, whenever the Purchaser’s participation to the Final Test will determine (for any cause or reason) an extension of the normal timing for the execution of such test, MEI shall not be responsible for any delay in the Delivery Date which, therefore, shall be adjusted accordingly.
Final Test. For a final test, operate the motor and/or pump under no load. Test the insulation resistance. Inspect the motor and/or pump for undue temperature, vibration and noise. Check the cooling fluid in submersible motors and/or pumps. Check for mechanical seal leaks, check for seal and thermal alarm operation. Correct any deficiency
Final Test. YIELD RECONCILIATION. Supplier and Buyer shall perform a final test yield reconciliation to adjust test services pricing on a monthly basis. The actual yield will be compared with the financial standard yield. The yield variance will be calculated as the delta between the financial standard cost yield used for setting standards and the actual yield. Adjustments made to correct yield transactions should also be taken into consideration. A credit or debit memo will be issued from the Supplier to Buyer.
Final Test. After the development is by over pumping and surging is complete, the well shall be tested for its performance, i.e yield characteristics and efficiency. This shall be achieved by conducting a step draw down test-determining draw down at the end of the hour by pumping at 5 to 8 different rates of discharge near the rated discharge. Preferably, the test should be conducted in a single day and the time of running of tubewell for each discharge shall be same say 1-2 hour. The data from the test can be used to determine the relative proportion of laminar and turbulent flow occurring, true efficiency and rated discharge of the well and working out the suitable parameter for the pump.
Final Test a) a) After the development is by over pumping and surging is complete the, the well shall be tested for its performance, i.e. yield characteristics and efficiency. This shall be achieved by conducting a step draw down test – determining draw down at the end of the hour by pumping at 5 to 8 different rates of discharge near the rated discharge. Preferably, the test should be conducted in a single day and the time of running of Tubewell for each discharge shall be same say 1 - 2 hour. The data from the test can be used to determine the relative proportion of laminar and turbulent flow occurring, true efficiency and rated discharge of the well and working out the suitable parameter for the pump. b) The performa attached at annexure-B is to be completed by the driller after the Tubewell has been completed. c) In case of any quantity of cement, steel, screen or any other controlled/ un-controlled, commodity issued to the contractor by the Engineer for use, directly in the aforesaid work or manufacture or material required in connection thereof, which is not utilized for the work for which it is issued and is otherwise disposed off by him or spoilt or lost or allowed to get deteriorated or used in excess of quantity actually required to be used as per specification herein stipulated or these fixed by the Engineer, the cost of such quantity of that material shall without prejudice to other rights and remedies available to the Govt. be recoverable from the contractor at double the stock issue rates at which it is able to be supplied to the contractor or at double the stock issue rates for quantity of material issued free of cost. The DWSS reserve the right to abandon a particular Tubewell due to lack of sufficient water bearing strata and the contractor will be paid at the rate quoted by the firm for Test Bore. If the T/well is to be abandoned due to caving or negligence of the contractor, nothing will be paid to the contractor. The decision of the EIC will be final and binding on the contractor. The Tubewell should be handed over to the DWSS in the complete shape. The housing pipe should be closed by a well cap for the period between the completion of the Tubewell and the installation of the pump set. The cap should be of such a design that it is easily removable causing no damage to the housing pipe.

Related to Final Test

  • Acceptance Tests 11.1 If the Contract provides acceptance tests for Goods and/or the result of Services after their completion and/or delivery to the Purchaser, the acceptance shall only be considered as definitive when such tests have demonstrated the compliance of the Goods and/or the result of the Services to the requirements in the Contract. 11.2 Where the Contract provides for an acceptance procedure in the presence of both parties, at the successful completion of such procedure, the Purchaser shall issue the Supplier with an acceptance certificate which shall authorise the Supplier to invoice the Purchaser for any payment due on such acceptance. 11.3 The Purchaser shall at its discretion be entitled to issue and acceptancecertificate with reserves. The Supplier shall be obliged to remedy any non-conformities within the period set out in the acceptance certificate. Any payment which would otherwise have been due on acceptance may be withheld by the Purchaser in whole or part until the non- conformities underlying the reserves have been remedied.

  • Performance Tests Contractor shall perform Performance Tests in accordance with Section 11.2 of the Agreement and Attachment S.

  • Performance Testing (a) All performance tests of the Project, including any Initial Performance Test required in Section 2 of Appendix VIII, will be performed in accordance with the test procedures set forth in Appendix VIII (“Performance Test”), including additional procedures and protocols related to Performance Testing as mutually agreed between Buyer and Seller (“Test Procedures”). Seller shall bear all costs and receive all revenues, if applicable, associated with all Performance Tests. (b) After the Initial Delivery Date and during the Delivery Term, Buyer will have the right to conduct a Performance Test (“Buyer Performance Test”) no more than once a calendar year to demonstrate whether the Project is capable of delivering the Distribution Services at the Contract Capacity. Within 30 calendar days following a Buyer Performance Test, Seller will have the right to retest the Project with a Performance Test (“Seller Retest”). For the avoidance of doubt, the results of any Seller Retest will supersede the results of the preceding Buyer Performance Test. (i) If a Buyer Performance Test or, if a corresponding Seller Retest has occurred, a Seller Retest demonstrates the Project is capable of delivering Distribution Services at or above ninety-nine percent (99%) of the Initial Contract Capacity, the Contract Capacity will remain the Initial Contract Capacity; (ii) If a Buyer Performance Test or, if a corresponding Seller Retest has occurred, a Seller Retest demonstrates the Project is capable of delivering Distribution Services at more than or equal to eighty-five (85%) of the Initial Contract Capacity, but less than ninety-nine percent (99%) of the Initial Contract Capacity (“Testing Band”), the Contract Capacity will be automatically adjusted (upwards or downwards) to the capacity commensurate with the amount of Distribution Services the Project delivered during the Performance Test within the Testing Band. (iii) If a Buyer Performance Test or, if a corresponding Seller Retest has occurred, a Seller Retest demonstrates the Project is not capable of delivering Distribution Services of at least eighty-five percent (85%) of the Initial Contract Capacity, an Event of Default shall occur in accordance with Section 7.1(a)(viii).

  • Acceptance Testing At the time of installation of a LIS trunk group, and at no additional charge, acceptance tests will be performed to ensure that the service is operational and meets the applicable technical parameters.

  • Stability Testing Patheon will conduct stability testing on the Products in accordance with the protocols set out in the Specifications for the separate fees and during the time periods set out in Schedule C. Patheon will not make any changes to these testing protocols without prior written approval from Client. If a confirmed stability test failure occurs, Patheon will notify Client within [***], after which Patheon and Client will jointly determine the proceedings and methods to be undertaken to investigate the cause of the failure, including which party will bear the cost of the investigation. Patheon will not be liable for these costs unless it has failed to perform the Manufacturing Services in accordance with the Specifications and cGMPs. Patheon will give Client all stability test data and results at Client’s request.