TAPING METHOD. Layers of insulating tape shall be applied to the length of the splice in opposite directions to a thickness of 1½ times the thickness of the cable insulation. The insulating tape shall be of the self-bonding type. Layers of jacket tape shall be applied over the insulation tape to a thickness of 1½ times the thickness of the cable jacket. The jacket tape shall be of the water-resisting type.
Appears in 3 contracts
Samples: a856-cityrecord.nyc.gov, a856-cityrecord.nyc.gov, a856-cityrecord.nyc.gov
TAPING METHOD. Layers of insulating tape shall be applied to the length of the splice in opposite directions to a thickness of 1½ 1 1/2 times the thickness of the cable insulation. The insulating tape shall be of the self-bonding type. .. Layers of jacket tape shall be applied over the insulation tape to a thickness of 1½ 1 1/2 times the thickness of the cable jacket. The jacket tape shall be of the water-water resisting type.
Appears in 2 contracts
TAPING METHOD. Layers of insulating tape shall be applied to the length of the splice in opposite directions to a thickness of 1½ 1 1/2 times the thickness of the cable insulation. The insulating tape shall be of the self-bonding type. Layers of jacket tape shall be applied over the insulation tape to a thickness of 1½ 1 1/2 times the thickness of the cable jacket. The jacket tape shall be of the water-water resisting type.
Appears in 1 contract
Samples: a856-cityrecord.nyc.gov