Routine Tests Sample Clauses
The "Routine Tests" clause establishes the requirement for regular or scheduled testing of products, systems, or processes to ensure they meet specified standards or performance criteria. Typically, this clause outlines the frequency, methods, and responsible parties for conducting such tests, and may specify the types of tests to be performed, such as quality control checks or safety inspections. By mandating routine testing, the clause helps maintain consistent quality, detect issues early, and ensure ongoing compliance with contractual or regulatory requirements.
Routine Tests. In accordance with the requirements of IEC 60137.
Routine Tests. All capacitor units shall be subjected to routine tests in accordance with IEC 60831-1&2. and must include (at least) following tests:
I. Capacitance measurement and output calculations II. Measurement of the tangent of the losses angle at evaluated temperature. III. Voltage test between terminals IV. Voltage test between terminals and container V. Test of the internal discharge device VI. Sealing test.
Routine Tests. All handling devices and lifting tackle supplied for maintenance purposes under this contract shall unless they are built into and form part of the equipment, be tested, marked and certificates of test provided. Lifting tackle built into and forming part of the equipment shall be operated with the maximum working load to the satisfaction of the Engineer.
Routine Tests. All other motors shall be submitted to test (a), (b), (c), (d) and (k) of the above.
Routine Tests. The following tests shall be conducted on each unit by the bidder at his works as per relevant standard - IS:7935/1975 (latest amended) :
a) Visual Examination ( Clause-4.4)
Routine Tests. FortisAlberta: FortisBC:
9.1 Finish Performance
Routine Tests. Routine tests and acceptance tests shall be as per the Quality Assurance Plan (QAP) approved by the Employer.
Routine Tests. Each completed transformer shall be subjected to following routine tests as per the latest edition of IEC 60076 unless specified otherwise.
(i) Measurement of winding resistance at each tap
(ii) Measurement of voltage ratio between HV and LV windings at each tap
(iii) Check of vector group
(iv) Measurement of no-load loss and no-load current
(v) Measurement of short-circuit impedance and load loss
(vi) Magnetic balance test as per CBIP manual publication no. 295
(vii) Separate source voltage withstand test
(viii) Induced over voltage withstand test
(ix) Measurement of insulation resistance
(x) Marshalling box functional test
(xi) IR Measurement on wiring of marshalling box 50 MW (AC) Solar PV Power Plants at Tamil Nadu Tender No. SECI/C&P/TD/2020/TN/50 TS Page 25 of 123 Signature of Bidder
(xii) Breakdown voltage test on transformer oil as per IS 335
(xiii) Oil leakage test on completely assembled transformer along with radiators
Routine Tests. Containers made of insulating material which have in service to withstand gas pressures in excess of atmospheric pressure shall each be tested hydraulically after all necessary grinding or machining work on them has been completed. For containers having fittings permanently attached thereto, the tests shall be made after the fittings have been added. The tests shall be carried out at the pressure given below for a period of 15 minutes and components shall thereafter be marked in an agreed manner.
(a) For containers subject to static gas pressure loads only, and not subject to material mechanical shock in service, the test shall be made at twice maximum working pressure.
(b) For containers subject to rapid changes of gas pressure, or gas pressure plus mechanical shock, the test shall be made at three times maximum working pressure.
Routine Tests. All components shall have been tested in accordance with relevant IEC recommendation or other standards prior to assembly in the complete equipment. Tests shall be carried out to prove the correct functioning and wiring of the complete equipment to the requirements of the specification. All secondary wiring including panel wiring and control circuits and all apparatus connected directly thereto shall withstand a high voltage test of 2 kV to earth unless subject to other requirements such as detailed under Protective Equipment.
