MW Generator Clause Samples
MW Generator. Qty. 1 Technical Data Packet (TDP) - To Include all system component mechanical drawings, assembly drawings, electrical drawings, PCB layouts, electronic control firmware executable and operator / maintenance manual. TDP shall be delivered in contractor / industry standard electronic format. Drawing levels shall be industry standard Level II, permitting third party manufacturers familiar with engine / generator production sufficient information to be able to manufacture.
MW Generator. The 1 MW generator shall consist of five (5) 200 kW generators as outlined above. A load management circuit shall be present to balance (rectify) all 5 outputs with regard to voltage and frequency and feed a main output bus. This approach permits all generators to behave as one as seen from the connected devices. In addition the load management circuit shall sense the required load and start up or shut down in 200 kW increments thereby enabling cost effectiveness in the situation of less than 1 MW output requirements. The 1 MW generator shall house the 5 200 kW generators on a single trailer capable of transit over regular highways with no additional special use permits. The housing shall encase all the 200 kW generators and be resistant to anticipated environmental operating conditions while providing protection from vandalism. As the 1 MW unit has potential deployment capability in third world nations a remote Globalstar GSP-1620 data modem shall be present to monitor output power consumption, unit tracking, permit remote diagnostics and permit remote shut down of the system allowing full incapacitation in the event of outstanding invoices.