Common use of Local Control Center, Metering and Telemetry Clause in Contracts

Local Control Center, Metering and Telemetry. Each Transmission Owner shall operate, or arrange for a suitable third party to operate, on a twenty-four (24) hour basis, a suitable control center, and shall install and maintain all other equipment and facilities reasonably required for the ISO to exercise Operational Control over Transmission Facilities Under ISO Operational Control. Operation of the NYS Power System will be a cooperative effort coordinated by the ISO control center in conjunction with each Transmission Owner's control center and will require the exchange of all reasonably necessary information. The Transmissions Owners’ control centers must provide the ISO with Supervisory Control and Data Acquisition (“SCADA”) information on facilities listed in Appendices A-1 and A-2 as well as on certain generation resources in their Transmission Districts. Each Transmission Owner shall have the responsibility for providing metering data in its Transmission District to the ISO, unless other parties are authorized by the appropriate regulatory authority to provide metering data. Each Transmission Owner shall be responsible for collecting and making available to the ISO billing quality metering data and any other information for the Transmission District required by the ISO for billing purposes. The Parties agree that the metering and data acquisition systems currently in place will be acceptable for initial ISO operation. The Transmission Owner shall cooperate with the ISO in implementing reasonable metering enhancements and new metering installations that the ISO may deem necessary, provided that mechanisms satisfactory to each Transmission Owner are in place for their recovery of all associated costs. Each Transmission Owner shall continue to receive telemetry from existing Generators in its Transmission District and provide for the receipt of such information from new Generators. Automatic Generation Control (“AGC”) will be implemented via each Transmission Owner’s control center. Each Transmission Owner shall operate its control center to comply with current AGC procedures, as well as any revised or new AGC procedures reasonably adopted by the ISO. In addition, each Transmission Owner shall provide backup control services to the ISO in the event the ISO’s computer systems malfunction. In such situations, Bid curves will be made available to the Transmission Owners’ control centers to facilitate the continued economic operation of the system. Each Transmission Owner will maintain a strict Code of Conduct to prevent such information from reaching any unauthorized person or entity.

Appears in 51 contracts

Samples: Iso Agreement, Transmission Owners, Transmission Owners

AutoNDA by SimpleDocs

Local Control Center, Metering and Telemetry. Each Transmission Owner The NTO shall operate, or arrange for a suitable third party pursuant to operateISO Tariffs, ISO Procedures, Reliability Rules and all other applicable reliability rules, standards and criteria on a twenty-four (24) hour basis, a suitable local control center, and shall install and maintain center(s) with all other equipment and facilities reasonably required for the ISO Service Agreement No. 2628 to exercise ISO Operational Control over NTO Transmission Facilities Under ISO Operational Control, and for the NTO to fulfill its responsibilities under this Agreement. The NTO shall maintain the local control center(s), as well as suitable backup operations, consistent with the Reliability Rules and all other applicable reliability rules, standards and criteria to permit the ISO, as the Transmission Operator, to meet its obligations. All NTO system operators in real- time communication with the ISO or responsible for directing real-time actions on NTO Transmission Facilities Under ISO Operational Control shall be required to maintain a NERC Transmission Operator or Reliability Operator certificate. Operation of the NYS Power System will be is a cooperative effort coordinated by the ISO control center in conjunction with each Transmission Owner's local control center centers and will require the exchange of all reasonably necessary information. The Transmissions Owners’ control centers must provide the ISO with NTO shall maintain Supervisory Control and Data Acquisition (“SCADA”) systems and provide the ISO with SCADA information on facilities listed in Appendices A-1 and A-2 herein as well as on certain generation and merchant transmission resources in their Transmission Districtsinterconnected to the NTO’s transmission facilities pursuant to the ISO OATT. Each Transmission Owner The NTO shall have the responsibility for providing provide metering data in for its Transmission District transmission facilities to the ISO, unless other parties are authorized by the appropriate regulatory authority to provide metering data. Each Transmission Owner The NTO shall be responsible for collecting collect and making available submit to the ISO billing quality metering data and any other information for the Transmission District its transmission facilities required by the ISO for billing purposes. The Parties agree that the metering and data acquisition systems currently in place will be acceptable for initial ISO operation. The Transmission Owner NTO shall cooperate with provide to the ISO in implementing reasonable metering enhancements the telemetry and new metering installations other operating data from generation and merchant transmission resources interconnected to its transmission facilities that the ISO may deem necessary, provided that mechanisms satisfactory to each Transmission Owner are in place for their recovery of all associated costs. Each Transmission Owner shall continue to receive telemetry from existing Generators in its Transmission District and provide requires for the receipt of such information from new Generators. Automatic Generation Control (“AGC”) will be implemented via each Transmission Owner’s control center. Each Transmission Owner shall operate its control center to comply with current AGC procedures, as well as any revised or new AGC procedures reasonably adopted by the ISO. In addition, each Transmission Owner shall provide backup control services to the ISO in the event the ISO’s computer systems malfunction. In such situations, Bid curves will be made available to the Transmission Owners’ control centers to facilitate the continued economic operation of the systemNYS Power System. Each Transmission Owner The NTO will establish and maintain a strict Code code of Conduct conduct to prevent such information from reaching any unauthorized person or entity.. Service Agreement No. 2628

Appears in 3 contracts

Samples: Service Agreement, Operating Agreement, Operating Agreement

Local Control Center, Metering and Telemetry. Each Transmission Owner OwnerThe NTO shall operate, or arrange for a suitable third party partyits ITO(s) to operate, pursuant to all applicable ISO Tariffs and ISO Procedures and all applicable reliability standards, criteria and rules on a twenty-four (24) hour basis, a suitable local control center, and shall install and maintain all other othercenter(s) with all equipment and facilities reasonably required for the ISO to exercise ISO Operational Control over NTO Transmission Facilities Under ISO Operational Control, and for the NTO to fulfill its responsibilities under this Agreement. Operation of the NYS Power System will be beis a cooperative effort coordinated by the ISO control center in conjunction with each Transmission Owner's Owner'slocal control center centercenters and will require the exchange of all reasonably necessary information. The Transmissions Owners’ control centers must mustNTO shall provide the ISO ISO, or arrange for its ITO(s) to provide the ISO, with Supervisory Control and Data Acquisition (“SCADA”) information on facilities listed in Appendices A-1 and A-2 herein as well as on certain generation and merchant transmission resources in their Transmission DistrictsDistrictsinterconnected to the NTO’s transmission facilities pursuant to the ISO OATT. Each Transmission Owner shall have the responsibility for providing metering data in its Transmission District to the ISO, unless other parties are authorized by the appropriate regulatory authority to provide metering data. Each Transmission Owner shall be responsible for collecting and making available to the ISO billing quality metering data and any other information for the Transmission District required by the ISO for billing purposes. The Parties agree that the metering and data acquisition systems currently in place will be acceptable for initial ISO operation. The Transmission Owner shall cooperate with the ISO in implementing reasonable metering enhancements and new metering installations that the ISO may deem necessary, provided that mechanisms satisfactory to each Transmission Owner are in place for their recovery of all associated costs. Each Transmission Owner shall continue to receive telemetry from existing Generators in its Transmission District and provide for the receipt of such information from new Generators. Automatic Generation Control (“AGC”) will be implemented via each Transmission Owner’s control center. Each Transmission Owner shall operate its control center to comply with current AGC procedures, as well as any revised or new AGC procedures reasonably adopted by the ISO. In addition, each Transmission Owner shall provide backup control services to the ISO in the event the ISO’s computer systems malfunction. In such situations, Bid curves will be made available to the Transmission Owners’ control centers to facilitate the continued economic operation of the system. Each Transmission Owner will maintain a strict Code of Conduct to prevent such information from reaching any unauthorized person or entity.. The NTO shall provide, or arrange for its ITO(s) to provide, metering data for its transmission facilities to the ISO, unless other parties are authorized by the appropriate regulatory authority to provide metering data. The NTO shall collect and submit to the ISO, or arrange for its ITO(s) to collect and submit to the ISO, billing quality metering data and any other information for its transmission facilities required by the ISO for billing purposes. The NTO shall provide to the ISO, or arrange for its ITO(s) to provide to the ISO, the telemetry and other operating data from generation and merchant transmission resources interconnected to its transmission facilities that the ISO requires for the operation of the NYS Power System. The NTO will establish and maintain a strict code of conduct to prevent such information from reaching any unauthorized person or entity. Formatted: Bullets and Numbering

Appears in 1 contract

Samples: Operating Agreement

Local Control Center, Metering and Telemetry. Each Transmission Owner OwnerThe NTO shall operate, or arrange for a suitable third party partyan ITO to operate, on a twenty-four (24) hour basis, a suitable local control center, and shall install and maintain all other with all equipment and facilities reasonably required for the ISO to exercise Operational Control over Transmission Facilities Under ISO Operational Control, and for the NTO to fulfill its responsibilities under this Agreement. Operation of the NYS Power System will be beis a cooperative effort coordinated by the ISO control center in conjunction with each Transmission Owner's Owner'slocal control center centercenters and will require the exchange of all reasonably necessary information. The Transmissions Owners’ Owners’local control centers centerscenter designated by the NTO and ITO for the NTO facilities must provide the ISO with Supervisory Control and Data Acquisition (“SCADA”) information on facilities listed in Appendices A-1 and A-2 as well as on certain generation and merchant transmission resources in their Transmission DistrictsDistrictsinterconnected to the NTO’s transmission facilities pursuant to the ISO OATT. Each Transmission Owner shall have the responsibility for providing metering data in its Transmission District to the ISO, unless other parties are authorized by the appropriate regulatory authority to provide metering data. Each Transmission Owner shall be responsible for collecting and making available to the ISO billing quality metering data and any other information for the Transmission District required by the ISO for billing purposes. The Parties agree that the metering and data acquisition systems currently in place will be acceptable for initial ISO operation. The Transmission Owner shall cooperate with the ISO in implementing reasonable metering enhancements and new metering installations that the ISO may deem necessary, provided that mechanisms satisfactory to each Transmission Owner are in place for their recovery of all associated costs. Each Transmission Owner shall continue to receive telemetry from existing Generators in its Transmission District and provide for the receipt of such information from new Generators. Automatic Generation Control (“AGC”) will be implemented via each Transmission Owner’s control center. Each Transmission Owner shall operate its control center to comply with current AGC procedures, as well as any revised or new AGC procedures reasonably adopted by the ISO. In addition, each Transmission Owner shall provide backup control services to the ISO in the event the ISO’s computer systems malfunction. In such situations, Bid curves will be made available to the Transmission Owners’ control centers to facilitate the continued economic operation of the system. Each Transmission Owner will maintain a strict Code of Conduct to prevent such information from reaching any unauthorized person or entity. The NTO shall arrange for the designated local control center to provide metering data for its transmission facilities to the ISO, unless other parties are authorized by the appropriate regulatory authority to provide metering data. The NTO shall arrange for the collection and submittal by the designated local control center to the ISO of billing quality metering data and any other information for its transmission facilities required by the ISO for billing purposes. The NTO shall arrange for the designated local control center to provide to the ISO the telemetry and other operating data from generation and merchant transmission resources interconnected to its transmission facilities that the ISO requires for the operation of the NYS Power System. The NTO will establish and maintain a strict Code of Conduct to prevent such information from reaching any unauthorized person or entity.

Appears in 1 contract

Samples: Operating Agreement

AutoNDA by SimpleDocs

Local Control Center, Metering and Telemetry. Each Transmission Owner shall operate, or arrange for a suitable third party to operate, on a twenty-four (24) hour basis, a suitable control center, and shall install and maintain all other equipment and facilities reasonably required for the ISO to exercise Operational Control over Transmission Facilities Under ISO Operational Control. Operation of the NYS Power System will be a cooperative effort coordinated by the ISO control center in conjunction with each Transmission Owner's control center and will require the exchange of all reasonably necessary information. The Transmissions Owners' control centers must provide the ISO with Supervisory Control and Data Acquisition ("SCADA") information on facilities listed in Appendices A-1 and A-2 as well as on certain generation resources in their Transmission Districts. Each Transmission Owner shall have the responsibility for providing metering data in its Transmission District to the ISO, unless other parties are authorized by the appropriate regulatory authority to provide metering data. Each Transmission Owner shall be responsible for collecting and making available to the ISO billing quality metering data and any other information for the Transmission District required by the ISO for billing purposes. The Parties agree that the metering and data acquisition systems currently in place will be acceptable for initial ISO operation. The Transmission Owner shall cooperate with the ISO in implementing reasonable metering enhancements and new metering installations that the ISO may deem necessary, provided that mechanisms satisfactory to each Transmission Owner are in place for their recovery of all associated costs. Each Transmission Owner shall continue to receive telemetry from existing Generators in its Transmission District and provide for the receipt of such information from new Generators. Automatic Generation Control ("AGC") will be implemented via each Transmission Owner’s 's control center. Each Transmission Owner shall operate its control center to comply with current AGC procedures, as well as any revised or new AGC procedures reasonably adopted by the ISO. In addition, each Transmission Owner shall provide backup control services to the ISO in the event the ISO’s 's computer systems malfunction. In such situations, Bid curves will be made available to the Transmission Owners' control centers to facilitate the continued economic operation of the system. Each Transmission Owner will maintain a strict Code of Conduct to prevent such information from reaching any unauthorized person or entity.. 2.06

Appears in 1 contract

Samples: Agreement (New York State Electric & Gas Corp)