Line structures Clause Samples

Line structures. Structures will be designed for the layouts indicated in section 3.1. 1. They will be of the lattice type and self-supported. The 500 kV structures shall carry not less than four conductors per phase and two (02) guy wires, one of the OPGW type and the other of the conventional type. Structures in 220 kV will have at least two conductors per phase and two (02) guy wires, one of the OPGW type and the other of the conventional type.
Line structures. Structures shall be designed for the layouts indicated in section 3.1.1, of the lattice-type and self-supported. The 220 kV structures of the new line shall have at least one conductor per phase and two guard cables: one of the OPGW-type and the other in EHS galvanized steel with a minimum rated section of 70 mm2.
Line structures. The structures will be designed for the configurations indicated in Paragraph 4.