Dynamic Performance Study. (a) A detailed Dynamic Performance Study (“DPS”) shall be performed to verify that the response to disturbances does not cause instability in the Merchant Transmission Facility, does not cause conditions that will damage the equipment and does behave according to the Merchant Transmission Facility design. The DPS report shall provide descriptions of the performance to the cases listed below where applicable. The case descriptions shall include the simulation setup and plots of relevant AC and DC quantities. System data needed for the simulations described below shall be obtained from Connecting Transmission Owner. 1. DPS Case Permanent DC Temporary AC side faults with one reclose, single-phase and three-phase Stuck AC breaker faults, single-phase and three-phase Switching to energize nearby power transformers, shunt capacitors, and shunt reactors Switching of AC filters and bus voltage control devices by the Reactive Power Control at the converter stations