Common use of Current levels Clause in Contracts

Current levels. All 138 kV and 22.9 kV switchgear (circuit breakers and disconnectors) shall meet the following characteristics: 138 kV 22.9 kV Minimum rated current 800 A 800 A Three-phase short-circuit breaking capacity, 1s 31.5 kA 25 kA

Appears in 2 contracts

Samples: STS Concession Contract, www.proyectosapp.pe

AutoNDA by SimpleDocs

Current levels. All 138 kV and 22.9 kV switchgear (circuit breakers and disconnectors) shall meet the following characteristics: 138 . 220 kV 60 kV 22.9 kV Minimum rated current 800 2500 A 800 1250 A 1250 A Three-phase short-circuit breaking capacity, 1s 40 kA 31.5 kA 25 kA

Appears in 1 contract

Samples: STS Concession Contract

AutoNDA by SimpleDocs

Current levels. All 138 kV and 22.9 kV switchgear (circuit breakers and disconnectors) shall meet the following characteristics: 138 . 220 kV 60 kV 22.9 kV Minimum rated current 800 2000 A 800 1250 A 1250 A Three-phase short-circuit breaking capacity, 1s 40 kA 31.5 kA 25 kA

Appears in 1 contract

Samples: STS Concession Contract