Common use of Wind Generating Facility Output Reduction Clause in Contracts

Wind Generating Facility Output Reduction. To protect the reliability of the Transmission System, a Generating Facility that is a wind plant shall be capable of reducing its generation output in increments of no more than fifty (50) MW in five (5) minute intervals. The requirements may be met by using: (a) SCADA control of circuit breakers protecting wind farm collector distribution circuits,

Appears in 4 contracts

Samples: Generator Interconnection Agreement, Generator Interconnection Agreement, Generator Interconnection Agreement

AutoNDA by SimpleDocs

Wind Generating Facility Output Reduction. To protect the reliability of the Transmission System, a Generating Facility generating facility that is a wind plant shall be capable of reducing its generation output in increments of no more than fifty (50) MW in five (5) minute intervals. The requirements may be met by using: (a) SCADA control of circuit breakers protecting wind farm collector distribution circuits,

Appears in 1 contract

Samples: Generator Interconnection Agreement

AutoNDA by SimpleDocs

Wind Generating Facility Output Reduction. To protect the reliability of the Transmission System, a Generating Facility that is a wind plant shall be capable of reducing its generation output in increments of no more than fifty (50) MW in five (5) minute intervals. The requirements may be met by using: (a) SCADA control of circuit breakers protecting wind farm collector distribution circuits,:

Appears in 1 contract

Samples: Interim Generator Interconnection Agreement