Voltage Support. Except as otherwise agreed by the Parties, unless Pacific Gas and Electric Company directs NCPA to maintain a specific voltage at any Point of MSS Interconnection for a NCPA or MSSAA Member Generating Unit, NCPA shall maintain the voltage on NCPA’s System so that reactive flows at the Points of MSS Interconnection are within the power factor band of 0.97 lag to
Appears in 1 contract
Sources: Ncpa MSS Aggregator Agreement
Voltage Support. Except as otherwise agreed by the Parties, unless Pacific Gas and Electric Company directs NCPA to maintain a specific voltage at any Point of MSS Interconnection for a NCPA or MSSAA Member Generating Unit, NCPA shall maintain the voltage on NCPA’s System so that reactive flows at the Points of MSS Interconnection are within the power factor band of 0.97 lag toto 0.99 lead. NCPA shall not be compensated for maintaining the power factor at the levels required by this Section 8.3 within this bandwidth. If NCPA fails to maintain the power factor at the levels specified by this Section 8.3, NCPA’s Scheduling Coordinator shall bear a portion of the CAISO’s Voltage Support costs.
Appears in 1 contract
Sources: Ncpa MSS Aggregator Agreement