Common use of Voltage and Power Quality Screen Clause in Contracts

Voltage and Power Quality Screen. In aggregate with existing generation on the line section: (1) the voltage regulation on the line section can be maintained in compliance with relevant requirements under all system conditions; (2) the voltage fluctuation is within acceptable limits as defined by Institute of Electrical and Electronics Engineers (IEEE) Standard 1453, or utility practice similar to IEEE Standard 1453; and (3) the harmonic levels meet IEEE Standard 519 limits.

Appears in 2 contracts

Samples: starw1.ncuc.net, www.oatioasis.com

AutoNDA by SimpleDocs

Voltage and Power Quality Screen. In aggregate with existing generation on the line section: (1) the voltage regulation on the line section can be maintained in compliance with relevant requirements under all system conditions; (2) the voltage fluctuation is within acceptable limits as defined by Institute of Electrical and Electronics Engineers (IEEE) Standard 1453, or utility practice similar to IEEE Standard 1453; and (3) the harmonic levels meet IEEE Standard 519 limits.;

Appears in 2 contracts

Samples: Facilities Study Agreement, Facilities Study Agreement

AutoNDA by SimpleDocs

Voltage and Power Quality Screen. In aggregate with existing generation on the line section: (1) the voltage regulation on the line section can be maintained in compliance with relevant requirements under all system conditions; (2) the voltage fluctuation fluctuations is within acceptable limits as defined by Institute of Electrical and Electronics Engineers (IEEE) Standard 1453, or utility practice similar to IEEE Standard 1453; and (3) the harmonic levels meet IEEE Standard 519 limits.

Appears in 2 contracts

Samples: Interconnection Agreement, Interconnection Agreement

Time is Money Join Law Insider Premium to draft better contracts faster.