Common use of Transmission Capacity in Emergency Condition Clause in Contracts

Transmission Capacity in Emergency Condition. In SEIN emergency conditions, for a period of up to thirty (30) minutes, the transmission line shall be capable of withstanding an overload not less than 30% above the Thermal Limit Transmission Capacity. A temperature of more than 75 ºC shall be admitted in the conductor, during the above- mentioned period, keeping the safety distances set out in the applicable standards.

Appears in 4 contracts

Samples: STS Concession Contract, STS Concession Contract, STS Concession Contract

AutoNDA by SimpleDocs

Transmission Capacity in Emergency Condition. In SEIN emergency conditionsconditions of the SEIN, and for a period of up to thirty (30) minutes, the transmission line shall be capable of withstanding withstand an overload overcharge not less than 30% above the Thermal Limit Transmission Capacity96 MVA. A temperature of more higher than 75 ºC shall will be admitted in the conductor, during the above- mentioned indicated period, keeping preserving the safety security distances set out established in the applicable standards.

Appears in 1 contract

Samples: www.proyectosapp.pe

AutoNDA by SimpleDocs
Time is Money Join Law Insider Premium to draft better contracts faster.