Substations. Generally, specifications of equipment in this subsection must be respected, and any modification or change to them proposed by the Concessionaire must be previously reviewed and approved by the Grantor. Yard equipment specifications shall comply with voltage and current levels indicated in paragraph c) Voltage and Insulation Levels and d) Current levels of section 2.3.4. a) They must comply with the minimum design criteria established in ▇▇▇▇▇▇▇ ▇, ▇▇▇▇▇ ▇ ▇▇ ▇▇- ▇▇. b) The corresponding IEC standards will be applied for each equipment and / or those that comply with them. c) Cabinets and control boxes shall have an IP-54 degree of protection. d) All metal parts shall be hot galvanized according to ASTM or VDE Standards, and windings shall be of insulated copper. e) Circuit breakers
Appears in 2 contracts
Substations. Generally, specifications of equipment in this subsection must be respected, and any modification or change to them proposed by the Concessionaire must be previously reviewed and approved by the Grantor. .
a) Yard equipment specifications shall comply with voltage and current levels indicated in paragraph c) Voltage and Insulation Levels and d) Current levels of section pursuant to subsection 2.3.4.
ab) They must comply with the minimum design criteria established in ▇▇▇▇▇▇▇ ▇Chapter 1, ▇▇▇▇▇ ▇ ▇▇ ▇▇- ▇▇Annex 1 of PR-20.
bc) The corresponding IEC standards will be applied for each equipment and / or those that comply with them.
cd) Cabinets and control boxes shall have an IP-54 degree of protection.
de) All metal parts shall be hot dip galvanized according to ASTM or VDE Standards, and the windings shall be made of insulated copper.
e) Circuit breakers
Appears in 1 contract
Sources: SGT Concession Agreement
Substations. GenerallyIn general, the equipment specifications of equipment contained in this subsection must section shall be respected, and any modification amendment or change made to them proposed by the Concessionaire must Concession Holder or the holders of concessions of the substation, as appropriate, shall be previously reviewed and approved by the Grantor. Yard The yard equipment specifications shall comply with meet the voltage and current levels indicated set out in paragraph c) Voltage and Insulation Levels and d) Current levels of section 2.3.4.subparagraph
a) They must comply with shall meet the minimum design criteria established set out in ▇▇▇▇▇▇▇ ▇Chapter 1, ▇▇▇▇▇ ▇ ▇▇ ▇▇- ▇▇Annex 1 of PR-20.
b) The corresponding IEC standards will be applied for applicable to each equipment and / or those and/or that comply with themthem shall be applied.
c) Cabinets The shelves and control boxes shall have an IP-54 degree of protectionprotection degree.
d) All metal parts shall be hot hot-dip galvanized according to the ASTM or VDE Standardsstandards, and the windings shall be made of insulated copper.
e) Circuit breakers
Appears in 1 contract
Sources: Concession Contract