Common use of Site Tests Clause in Contracts

Site Tests. After erection is completed following test shall be conducted. (i) Insulation resistance of the generator. (ii) Speed no load voltage and full load voltage regulation (iii) Frequency on no load half load and full load (iv) Full load test for 6 hrs at rated voltage, speed & frequency The readings shall be observed with calibrated meter. Only meter shall be used for the test. The reading shall be properly tabulated submitted in triplicate to the Independent Engineer.