Server Room. Developer shall provide one computer server room (100 square feet) that 14 has limited and controlled access and is locked via security card access. The server 15 room must be accessible via a hallway entry not sharing any walls with the exterior of 16 the building and must have no windows, a non-static floor covering, and at least three 17 dedicated isolated ground 20-amp power circuits and one dedicated isolated ground 30- 18 amp circuit. Developer shall locate all patch panels (phone and data) within the 19 designated server room. Developer shall maintain server room temperature with a 20 dedicated air-conditioning/cooling system, as described above. Developer shall provide 21 uninterruptable power supply (UPS) system in the server room capable of providing 22 spike and xxxxx out protection for all Developer and ADOT server room equipment.

Appears in 4 contracts

Samples: apps.azdot.gov, apps.azdot.gov, apps.azdot.gov

AutoNDA by SimpleDocs

Server Room. Developer shall provide one computer server room (100 square feet) that 14 40 has limited and controlled access and is locked via security card access. The server 15 41 room must be accessible via a hallway entry not sharing any walls with the exterior of 16 42 the building and must have no windows, a non-static floor covering, and at least three 17 43 dedicated isolated ground 20-amp power circuits and one dedicated isolated ground 30- 18 44 amp circuit. Developer shall locate all patch panels (phone and data) within the 19 45 designated server room. Developer shall maintain server room temperature with a 20 46 dedicated air-conditioning/cooling system, as described above. Developer shall provide 21 1 uninterruptable power supply (UPS) system in the server room capable of providing 22 2 spike and xxxxx out protection for all Developer and ADOT server room equipment.

Appears in 3 contracts

Samples: apps.azdot.gov, apps.azdot.gov, apps.azdot.gov

Server Room. Developer shall provide one computer server room (100 square feet) that 14 46 has limited and controlled access and is locked via security card access. The server 15 1 room must be accessible via a hallway entry not sharing any walls with the exterior of 16 2 the building and must have no windows, a non-static floor covering, and at least three 17 3 dedicated isolated ground 20-amp power circuits and one dedicated isolated ground 30- 18 4 amp circuit. Developer shall locate all patch panels (phone and data) within the 19 5 designated server room. Developer shall maintain server room temperature with a 20 6 dedicated air-conditioning/cooling system, as described above. Developer shall provide 21 7 uninterruptable power supply (UPS) system in the server room capable of providing 22 8 spike and xxxxx out protection for all Developer and ADOT server room equipment.

Appears in 1 contract

Samples: apps.azdot.gov

Server Room. Developer shall provide one computer server room (100 square feet) that 14 42 has limited and controlled access and is locked via security card access. The server 15 43 room must be accessible via a hallway entry not sharing any walls with the exterior of 16 44 the building and must have no windows, a non-static floor covering, and at least three 17 45 dedicated isolated ground 20-amp power circuits and one dedicated isolated ground 30- 18 46 amp circuit. Developer shall locate all patch panels (phone and data) within the 19 47 designated server room. Developer shall maintain server room temperature with a 20 48 dedicated air-conditioning/cooling system, as described above. Developer shall provide 21 1 uninterruptable power supply (UPS) system in the server room capable of providing 22 2 spike and xxxxx out protection for all Developer and ADOT stakeholder server room 3 equipment.

Appears in 1 contract

Samples: apps.azdot.gov

Server Room. Developer shall provide one computer server room (100 square feet) that 14 44 has limited and controlled access and is locked via security card access. The server 15 45 room must be accessible via a hallway entry not sharing any walls with the exterior of 16 46 the building and must have no windows, a non-static floor covering, and at least three 17 1 dedicated isolated ground 20-amp power circuits and one dedicated isolated ground 30- 18 2 amp circuit. Developer shall locate all patch panels (phone and data) within the 19 3 designated server room. Developer shall maintain server room temperature with a 20 4 dedicated air-conditioning/cooling system, as described above. Developer shall provide 21 5 uninterruptable power supply (UPS) system in the server room capable of providing 22 6 spike and xxxxx brown out protection for all Developer and ADOT server room equipment.

Appears in 1 contract

Samples: apps.azdot.gov

Server Room. Developer shall provide one computer server room (100 square feet) that 14 32 has limited and controlled access and is locked via security card access. The server 15 33 room must be accessible via a hallway entry not sharing any walls with the exterior of 16 34 the building and must have no windows, a non-static floor covering, and at least three 17 35 dedicated isolated ground 20-amp power circuits and one dedicated isolated ground 30- 18 36 amp circuit. Developer shall locate all patch panels (phone and data) within the 19 37 designated server room. Developer shall maintain server room temperature with a 20 38 dedicated air-conditioning/cooling system, as described above. Developer shall provide 21 39 uninterruptable power supply (UPS) system in the server room capable of providing 22 40 spike and xxxxx out protection for all Developer and ADOT stakeholderADOT server room 41 equipment.

Appears in 1 contract

Samples: apps.azdot.gov

AutoNDA by SimpleDocs

Server Room. Developer shall provide one computer server room (100 square feet) that 14 has limited and controlled access and is locked via security card access. The server 15 room must be accessible via a hallway entry not sharing any walls with the exterior of 16 the building and must have no windows, a non-static floor covering, and at least three 17 dedicated isolated ground 20-amp power circuits and one dedicated isolated ground 30- 18 amp circuit. Developer shall locate all patch panels (phone and data) within the 19 designated server room. Developer shall maintain server room temperature with a 20 dedicated air-conditioning/cooling system, as described above. Developer shall provide 21 uninterruptable power supply (UPS) system in the server room capable of providing 22 spike and xxxxx brown out protection for all Developer and ADOT server room equipment.

Appears in 1 contract

Samples: apps.azdot.gov

Server Room. Developer shall provide one computer server room (100 square feet) that 14 9 has limited and controlled access and is locked via security card access. The server 15 10 room must be accessible via a hallway entry not sharing any walls with the exterior of 16 11 the building and must have no windows, a non-static floor covering, and at least three 17 12 dedicated isolated ground 20-amp power circuits and one dedicated isolated ground 30- 18 13 amp circuit. Developer shall locate all patch panels (phone and data) within the 19 14 designated server room. Developer shall maintain server room temperature with a 20 15 dedicated air-conditioning/cooling system, as described above. Developer shall provide 21 16 uninterruptable power supply (UPS) system in the server room capable of providing 22 17 spike and xxxxx out protection for all Developer and ADOT stakeholder server room 18 equipment.

Appears in 1 contract

Samples: apps.azdot.gov

Server Room. Developer shall provide one computer server room (100 square feet) that 14 40 has limited and controlled access and is locked via security card access. The server 15 41 room must be accessible via a hallway entry not sharing any walls with the exterior of 16 42 the building and must have no windows, a non-static floor covering, and at least three 17 43 dedicated isolated ground 20-amp power circuits and one dedicated isolated ground 30- 18 44 amp circuit. Developer shall locate all patch panels (phone and data) within the 19 45 designated server room. Developer shall maintain server room temperature with a 20 46 dedicated air-conditioning/cooling system, as described above. Developer shall provide 21 1 uninterruptable power supply (UPS) system in the server room capable of providing 22 2 spike and xxxxx brown out protection for all Developer and ADOT server room equipment.

Appears in 1 contract

Samples: apps.azdot.gov

Time is Money Join Law Insider Premium to draft better contracts faster.