Reactive Power Capability Clause Samples
POPULAR SAMPLE Copied 1 times
Reactive Power Capability. AT HV SIDE OF STEP-UP TRANSFORMER (at SUMMARY TABLE C RATED MW LEAD (Mvar) LAG (Mvar)
Reactive Power Capability. This table should be completed to reflect the combination of the DER Unit’s capability and any limitation in the DER Unit’s Connection Agreement with UKPN. Consistent with clause 10, if there is any change in the DER Unit’s capability, an update of this schedule may be required. Above capability plotted as a P/Q chart if available (Performance Chart) Figure 1: Illustration of P/Q chart Please refer to the examples in the Market Procedures when providing performance charts. PQ capability charts have to be defined at the point of connection (POC) for non-synchronous DER and at the generator terminals for synchronous DER.
Reactive Power Capability. (Leading):
Reactive Power Capability. AND MINIMUM POWER FACTOR REQUIREMENTS
Reactive Power Capability. Power Quality Test as per IEC 61400-21;
Reactive Power Capability. The requirements of this Article apply to the steady state condition of the power system only, and do not apply to transient stability. The inner profile of Figure 9 of the RfG is further specified by the red dashed line in Figure d below, while respecting the figures of Table 11. The coordinates of the vertices of the red dashed profile of Figure d are: Signed for approval: ▇▇▇▇▇▇ ▇▇▇ ▇.▇.▇▇▇▇ November 4, 2015 PAGE 20 of 41 Figure d: The required P-Q/Pmax-profile of a power park modulean Offshore PPM at the cConnection pPoint by the active power The coordinates of the vertices of the red dashed profile of Figure d are: ▇▇▇▇▇▇ ▇▇▇ B.V. DATE October 8, 2015 PAGE 19 of 28 0,10 0,00 0,10 0,10 0,35 0,20 0,35 1,00 In case a Power Park ModuleOffshore PPM has a reactive power capability beyond the voltage range specified the capability shall not be deliberately limited. Limitation of reactive power capability based on the number of generating units in service may not influence the behaviour of the reactive power controller within these limited capabilities. During operation the PPM shall absorb or inject reactive power on demand of TenneT between -0,1 pu and +0,1 pu (1 pu is full active power in MW independent of the numbers of WTGs in operation) at PCC, as agreed in the CTA. If the reactive power capabilities of a specific WTG cannot comply at very low active power (below 0.1 pu), then TenneT will adjust their component set-up (reactors, capacitors) accordingly. The full reactive power capabilities of the PPM to absorb or inject reactive power on demand of TenneT are between -0,4 pu (absorption) and +0,35 pu (injection) at PCC (1 pu is full active power in MW dependent of the numbers of WTGs in operation). In addition to Article 25 and 21 of the RfG, Article 5.2.2.1 of the Dutch grid code (Netcode Elektriciteit) is also applicable:
Reactive Power Capability.
(1) The Generator must advise Essential Energy at least annually of the reactive power capability which the Generator intends to make available to Essential Energy to facilitate the transmission of real power and maintain acceptable network voltage levels, to the extent that it is not as specified in Item 3 of Schedule 2.
(2) The Generator must advise Essential Energy of any significant change in reactive power capability at any connection point; including the circumstances resulting from the change, as soon as possible after such a change occurs.
(3) Essential Energy may only use the information in this clause 12.2 for network planning and development purposes, to assess connection and network capability and performance and as required under the Rules.
Reactive Power Capability. The Facility shall be designed to supply power (MWAC) for power factors ranging between 0.9 lagging and 0.9 leading, measured at the Point of Delivery. The resulting Reactive Power requirement shall be available from 20% of the Maximum Capacity of the Facility at the Point of Delivery.
Reactive Power Capability. 1.1 In respect of each Despatch Unit, a Tenderer must nominate a Genset Registered Capacity which it anticipates will be the actual Genset Registered Capacity on the Contract Start Day for that Despatch Unit (in this Appendix 5 referred to as "the Nominated Genset Registered Capacity") to be used for the duration of the Market Agreement. All capability data used for the purpose of a Tender must be expressed as the capability of a Despatch Unit at the Commercial Boundary and must represent the value of Reactive Power output which can be supplied continuously at the Commercial Boundary when the Despatch Unit is operating at the Nominated Genset Registered Capacity.
1.2 In respect of each Despatch Unit, all capability data relating to the provision of the Enhanced Reactive Power Service specified in sub-paragraph 1.3(a) of this Schedule must be expressed as the capability of that Despatch Unit at the Commercial Boundary across a system voltage range to be specified by the Tenderer in its Tender (or otherwise in accordance with directions given by NGC).
Reactive Power Capability. (a) To facilitate the transmission of real power and maintain acceptable network voltage levels, you must make available to Ausgrid a reactive power capability which is no less than that specified in Item 3 of Schedule 5 to this agreement, or that required by section 5.2 of the NER; whichever is the greater.
(b) You must advise Ausgrid of any significant change in reactive power capability at any connection point, including the circumstances resulting from the change, as soon as possible after such a change occurs.
(c) Ausgrid may only use this information for network planning and development purposes, to assess connection and network capability and performance and as required under the Rules.
