Reactive Power Capability Sample Clauses

Reactive Power Capability. This table should be completed to reflect the combination of the DER Unit’s capability and any limitation in the DER Unit’s Connection Agreement with UKPN. Consistent with clause 10, if there is any change in the DER Unit’s capability, an update of this schedule may be required. Active Power Output P (MW) Lead Reactive Power capability Qmin (Mvar) Lag Reactive Power capability Qmax (Mvar) Above capability plotted as a P/Q chart if available (Performance Chart) Figure 1: Illustration of P/Q chart Please refer to the examples in the Market Procedures when providing performance charts. PQ capability charts have to be defined at the point of connection (POC) for non-synchronous DER and at the generator terminals for synchronous DER.
AutoNDA by SimpleDocs
Reactive Power Capability. (viii) Power Quality Test as per IEC 61400-21;
Reactive Power Capability. AT HV SIDE OF STEP-UP TRANSFORMER (at rated terminal and nominal system voltage) SUMMARY TABLE C RATED MW LEAD (Mvar) LAG (Mvar) CCGT UNIT Part II Meters and Aggregation Principles [BM Unit No.] [BM] or [CCGT] Unit No Meter Identification No. Meter Location Code Loss Adjustment Factor Aggregation Methodology [N/A] or [Category A/B/C* aggregation principles as set out in the latest published version of the document entitled “Methodology Document for the Aggregation of Reactive Power Metering” shall apply] * Delete as applicable Part III
Reactive Power Capability. (a) To facilitate the transmission of real power and maintain acceptable network voltage levels, you must make available to Ausgrid a reactive power capability which is no less than that specified in Item 3 of Schedule 5 to this agreement, or that required by section 5.2 of the NER; whichever is the greater.
Reactive Power Capability. The Generator must make available to Ausgrid a reactive power capability which is no less than as follows: [insert details]
Reactive Power Capability. For the purposes of settlement, the Reactive Power capability of the Generating Unit shall be determined separately for Reactive Power (Leading) and Reactive Power (Lagging) for each Trading Period as described in paragraphs 3.1.1 and 3.1.2. The Generating Unit will, for the purposes of this Schedule 3, only have Reactive Power Capability (Leading) or Reactive Power Capability (Lagging) when the Generating Unit is Synchronised to the power system and/or a Reactive Power Device is in service.
Reactive Power Capability. (Leading):
AutoNDA by SimpleDocs
Reactive Power Capability. 1.1 In respect of each Despatch Unit, a Tenderer must nominate a Genset Registered Capacity which it anticipates will be the actual Genset Registered Capacity on the Contract Start Day for that Despatch Unit (in this Appendix 5 referred to as "the Nominated Genset Registered Capacity") to be used for the duration of the Market Agreement. All capability data used for the purpose of a Tender must be expressed as the capability of a Despatch Unit at the Commercial Boundary and must represent the value of Reactive Power output which can be supplied continuously at the Commercial Boundary when the Despatch Unit is operating at the Nominated Genset Registered Capacity.
Reactive Power Capability. The Facility shall be designed to supply power (MWAC) for power factors ranging between 0.9 lagging and 0.9 leading, measured at the Point of Delivery. The resulting Reactive Power requirement shall be available from 20% of the Maximum Capacity of the Facility at the Point of Delivery.
Reactive Power Capability. This table should be completed to reflect the combination of the DER Unit’s capability and any limitation in the DER Unit’s Connection Agreement with UKPN. Consistent with clause 10, if there is any change in the DER Unit’s capability, an update of this schedule may be required.
Time is Money Join Law Insider Premium to draft better contracts faster.