Common use of Reactive Power Clause in Contracts

Reactive Power. 1.9.1 Interconnection customers with a distributed generation facility larger than or equal to 1 MVA shall design their distributed generation facilities to maintain a power factor at the point of interconnection between .95 lagging and .95 leading at all times. Interconnection customers with a distributed generation facility smaller than 1 MVA shall design their distributed generation facility to maintain a power factor at the point of interconnection between .90 lagging and .90 leading at all times.

Appears in 9 contracts

Samples: Feasibility Study Agreement, Feasibility Study Agreement, Standard Agreement

AutoNDA by SimpleDocs

Reactive Power. 1.9.1 Interconnection customers with a distributed generation DER facility larger than or equal to 1 MVA shall design their distributed generation DER facilities to maintain a power factor at the point of interconnection between .95 lagging and .95 leading at all times. Interconnection customers with a distributed generation DER facility smaller than 1 MVA shall design their distributed generation DER facility to maintain a power factor at the point of interconnection between .90 lagging and .90 leading at all times.

Appears in 1 contract

Samples: www.countyofkane.org

Reactive Power. 1.9.1 Interconnection customers with a distributed generation facility larger than or equal to 1 MVA shall design their distributed generation facilities to maintain a power factor at the point of interconnection between .95 0.95 lagging and .95 0.95 leading at all times. Interconnection customers with a distributed generation facility smaller than 1 MVA shall design their distributed generation facility to maintain a power factor at the point of interconnection between .90 0.90 lagging and .90 0.90 leading at all times.

Appears in 1 contract

Samples: Feasibility Study Agreement

Reactive Power. 1.9.1 Interconnection customers member-owners with a distributed generation facility larger than or equal to 1 MVA shall design their distributed generation facilities to maintain a power factor at the point of interconnection between .95 lagging and .95 leading at all times. Interconnection customers member- owners with a distributed generation facility smaller than 1 MVA shall design their distributed generation facility to maintain a power factor at the point of interconnection between .90 lagging and .90 leading at all times.

Appears in 1 contract

Samples: 4 Interconnection Agreement

AutoNDA by SimpleDocs

Reactive Power. 1.9.1 1.9.1. Interconnection customers with a distributed generation facility larger than or equal to 1 MVA shall design their distributed generation facilities to maintain a power factor at the point of interconnection between .95 lagging and .95 leading at all times. Interconnection customers with a distributed generation facility smaller than 1 MVA shall design their distributed generation facility to maintain a power factor at the point of interconnection between .90 lagging and .90 leading at all times.

Appears in 1 contract

Samples: www.icc.illinois.gov

Reactive Power. 1.9.1 Interconnection customers member-consumers with a distributed generation facility larger than or equal to 1 MVA shall design their distributed generation facilities to maintain a power factor at the point of interconnection between .95 lagging and .95 leading at all times. Interconnection customers member- consumers with a distributed generation facility smaller than 1 MVA shall design their distributed generation facility to maintain a power factor at the point of interconnection between .90 lagging and .90 leading at all times.

Appears in 1 contract

Samples: 4 Interconnection Agreement

Time is Money Join Law Insider Premium to draft better contracts faster.