Reactive Power. The Interconnection Customer shall design its Small Generator Facility to maintain a composite power delivery at continuous rated power output at the Point of Common Coupling at a power factor within the range of 0.95 leading to 0.95 lagging.
Appears in 8 contracts
Sources: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement
Reactive Power. The Interconnection Customer shall design its Small Generator Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Common Coupling at a power factor within the range of 0.95 leading to 0.95 lagging.
Appears in 6 contracts
Sources: Interconnection Agreement, Interconnection Agreement, Interconnection Agreement
Reactive Power. 1.8.1 The Interconnection Customer shall design its Small Generator Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Common Coupling Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the Utility has established different requirements that apply to all similarly situated generators in the control area on a comparable basis. The requirements of this paragraph shall not apply to wind generators.
Appears in 3 contracts
Sources: Interconnection Procedures, Interconnection Procedures, Interconnection Procedures
Reactive Power. 1.8.1 The Interconnection Customer shall design its Small Generator Generating Facility to maintain a composite power delivery at continuous rated power output at the Point terminals of Common Coupling each generating unit at a power factor within the range of 0.95 leading to 0.95 lagging.of
Appears in 3 contracts
Sources: Small Generator Interconnection Agreement (Sgia), Small Generator Interconnection Agreement, Small Generator Interconnection Agreement
Reactive Power. The Interconnection Customer Member shall design its Small Generator Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Common Coupling Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the Cooperative has established different requirements that apply to all similarly situated generators in the control area on a comparable basis. The requirements of this paragraph shall not apply to wind generators.
Appears in 1 contract
Sources: Interconnection Agreement
Reactive Power. 1.8.1 The Interconnection Customer shall design its Small Generator Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Common Coupling Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging, unless the Utility has established different requirements that apply to all similarly situated generators in the control area on a comparable basis.
Appears in 1 contract
Sources: Interconnection Agreement
Reactive Power. The Interconnection Customer shall design its Small Generator Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Common Coupling Interconnection at a all power factor within factors over the range of 0.95 leading to 0.95 lagging, unless GPA has established different requirements that apply to all similarly situated generators in the control area on a comparable basis. The Generating Facility shall be capable of continuous dynamic operation throughout the power factor design range as measured at the Point of Interconnection.
Appears in 1 contract
Reactive Power. The Interconnection Customer shall design its Small Generator Generating Facility to maintain a composite power delivery at continuous rated power output at the Point of Common Coupling Interconnection at a power factor within the range of 0.95 leading to 0.95 lagging., unless the City has established different requirements that apply to all similarly situated generators in the control area on a
Appears in 1 contract
Sources: Interconnection Agreement