Common use of Developer’s Attachment Facilities Clause in Contracts

Developer’s Attachment Facilities. “DAF”): The Merchant Transmission Facility shall interconnect at the available bus position of the Connecting Transmission Owner’s West 49th Street 345 kilovolt (“kV”) Gas Insulated Switchgear (“GIS”) substation (“Xxxx 00xx Xxxxxx Substation”) between existing circuit breakers 7 and 8. The DAF, as identified in Figure A-1, will be located between the Xxxx 00xx Xxxxxx Substation and the cable transition splice vault at West 52nd Street. Specifically, the DAF will be a single circuit, three phase, 345kV buried electric cable system comprised of (i) an approximately 1800 foot solid dielectric cable segment installed in the public roadways of New York City from the point at which it exits a cable transition splice vault on West 00xx Xxxxxx to a 345kV GIS design termination in the West 00xx Xxxxxx Substation; and (ii) all necessary terminations, splices and appurtenances as necessary to construct, operate and maintain the DAF. Figure A-1 identifies the DAF, Point of Change of Ownership, and the Point of Interconnection. Technical details of the major DAF equipment are as follows: