CULVERT INSTALLATION. 2.37.1 If the project is located in a moderate to very high Fire Hazard Severity Zone as designated by CAL FIRE, culvert materials should consist of corrugated metal pipe (CMP). Use of High-Density Polyethylene (HDPE) pipe is not recommended. 2.37.2 Existing fill material in the crossing shall be excavated down vertically to the approximate original channel and outwards horizontally to the approximate crossing hinge points (transition between naturally occurring soil and remnant temporary crossing fill material) to remove any potential unstable debris and voids in the older fill prism. 2.37.3 Culvert shall be installed to grade (not perched or suspended), aligned with the natural stream channel, and extend lengthwise completely beyond the toe of fill. If culvert cannot be set to grade, it shall be oriented in the lower third of the fill face, and a downspout or appropriately-sized energy dissipator (e.g., boulders, riprap, or rocks) shall be installed above or below the outfall as needed to effectively prevent stream bed, channel, or bank erosion (scouring, headcutting, or downcutting). The Permittee shall ensure basins are not constructed, and channels shall not be widened at culvert inlets. 2.37.4 Culvert bed shall be composed of either compacted rock-free soil or crushed gravel. Bedding beneath the culvert shall provide for even distribution of the load over the length of the culvert and allow for natural settling and compaction to help the culvert seat into a straight profile. The crossing backfill materials shall be free of rocks, limbs, or other debris that could allow water to seep around the culvert and shall be compacted. 2.37.5 Culvert inlet/outlet (including the outfall area) and fill faces shall be armored where stream flow, road runoff, or rainfall energy is likely to erode fill material and the outfall area. 2.37.6 Permanent culverts shall be sized to accommodate the estimated 100-year flood flow (i.e., ≥1.0 times the width of the bankfull channel width or the 100- year flood size, whichever is greater), including debris, culvert embedding, and sediment loads.
Appears in 1 contract
CULVERT INSTALLATION. 2.37.1 2.15.1 If the project is located in a moderate to very high Fire Hazard Severity Zone as designated by CAL FIRE, culvert materials should consist of corrugated metal pipe (CMP). Use of High-Density Polyethylene (HDPE) Notification #EPIMS-HUM-02552-R1 Streambed Alteration Agreement Page 7 of 14 pipe is not recommended.
2.37.2 2.15.2 Existing fill material in the crossing shall be excavated down vertically to the approximate original channel and outwards horizontally to the approximate crossing hinge points (transition between naturally occurring soil and remnant temporary crossing fill material) to remove any potential unstable debris and voids in the older fill prism.
2.37.3 2.15.3 Culvert shall be installed to grade (not perched or suspended), aligned with the natural stream channel, and extend lengthwise completely beyond the toe of fill. If culvert cannot be set to grade, it shall be oriented in the lower third of the fill face, and a downspout or appropriately-sized energy dissipator (e.g., boulders, riprap, or rocks) shall be installed above or below the outfall as needed to effectively prevent stream bed, channel, or bank erosion (scouring, headcutting, or downcutting). The Permittee shall ensure basins are not constructed, and channels shall not be widened at culvert inlets.
2.37.4 2.15.4 Culvert bed shall be composed of either compacted rock-free soil or crushed gravel. Bedding beneath the culvert shall provide for even distribution of the load over the length of the culvert and allow for natural settling and compaction to help the culvert seat into a straight profile. The crossing backfill materials shall be free of rocks, limbs, or other debris that could allow water to seep around the culvert and shall be compacted.
2.37.5 2.15.5 Culvert inlet/outlet (including the outfall area) and fill faces shall be armored where stream flow, road runoff, or rainfall energy is likely to erode fill material and the outfall area.
2.37.6 2.15.6 Permanent culverts shall be sized to accommodate the estimated 100-year flood flow (i.e., ≥1.0 times the width of the bankfull channel width or the 100- 100-year flood size, whichever is greater), including debris, culvert embedding, and sediment loads.
Appears in 1 contract
CULVERT INSTALLATION. 2.37.1 2.36.1 If the project is located in a moderate to very high Fire Hazard Severity Zone as designated by CAL FIRE, culvert materials should consist of corrugated metal pipe (CMP). Use of High-Density Polyethylene (HDPE) pipe is not recommended.
2.37.2 2.36.2 Existing fill material in the crossing shall be excavated down vertically to the approximate original channel and outwards horizontally to the approximate crossing hinge points (transition between naturally occurring soil and remnant temporary crossing fill material) to remove any potential unstable debris and voids in the older fill prism.
2.37.3 2.36.3 Culvert shall be installed to grade (not perched or suspended), aligned with the natural stream channel, and extend lengthwise completely beyond the toe of fill. If culvert cannot be set to grade, it shall be oriented in the lower Notification #EPIMS-HUM-22999-R1 Streambed Alteration Agreement Page 12 of 19 third of the fill face, and a downspout or appropriately-sized energy dissipator (e.g., boulders, riprap, or rocks) shall be installed above or below the outfall as needed to effectively prevent stream bed, channel, or bank erosion (scouring, headcutting, or downcutting). The Permittee shall ensure basins are not constructed, and channels shall not be widened at culvert inlets.
2.37.4 2.36.4 Culvert bed shall be composed of either compacted rock-free soil or crushed gravel. Bedding beneath the culvert shall provide for even distribution of the load over the length of the culvert and allow for natural settling and compaction to help the culvert seat into a straight profile. The crossing backfill materials shall be free of rocks, limbs, or other debris that could allow water to seep around the culvert and shall be compacted.
2.37.5 2.36.5 Culvert inlet/outlet (including the outfall area) and fill faces shall be armored where stream flow, road runoff, or rainfall energy is likely to erode fill material and the outfall area.
2.37.6 2.36.6 Permanent culverts shall be sized to accommodate the estimated 100-year flood flow (i.e., ≥1.0 times the width of the bankfull channel width or the 100- year flood size, whichever is greater), including debris, culvert embedding, and sediment loads.
Appears in 1 contract
CULVERT INSTALLATION. 2.37.1 2.40.1 If the project is located in a moderate to very high Fire Hazard Severity Zone as designated by CAL FIRE, culvert materials should consist of corrugated metal pipe (CMP). Use of High-Density Polyethylene (HDPE) pipe is not recommended.
2.37.2 2.40.2 Existing fill material in the crossing shall be excavated down vertically to the approximate original channel and outwards horizontally to the approximate crossing hinge points (transition between naturally occurring soil and remnant temporary crossing fill material) to remove any potential unstable debris and voids in the older fill prism.
2.37.3 2.40.3 Culvert shall be installed to grade (not perched or suspended), aligned with the natural stream channel, and extend lengthwise completely beyond the toe of fill. If culvert cannot be set to grade, it shall be oriented in the lower third of the fill face, and a downspout or appropriately-sized energy dissipator (e.g., boulders, riprap, or rocks) shall be installed above or below the outfall as needed to effectively prevent stream bed, channel, or bank erosion (scouring, headcutting, or downcutting). The Permittee shall ensure basins are not constructed, and channels shall not be widened at culvert inlets.
2.37.4 2.40.4 Culvert bed shall be composed of either compacted rock-free soil or crushed gravel. Bedding beneath the culvert shall provide for even distribution of the load over the length of the culvert and allow for natural settling and compaction to help the culvert seat into a straight profile. The crossing backfill materials shall be free of rocks, limbs, or other debris that could allow water to seep around the culvert and shall be compacted.. DocuSign Envelope ID: 2852C67F-8734-48AA-84C4-8ADCEA6A7503
2.37.5 2.40.5 Culvert inlet/outlet (including the outfall area) and fill faces shall be armored where stream flow, road runoff, or rainfall energy is likely to erode fill material and the outfall area.
2.37.6 2.40.6 Permanent culverts shall be sized to accommodate the estimated 100-year flood flow (i.e., ≥1.0 times the width of the bankfull channel width or the 100- year flood size, whichever is greater), including debris, culvert embedding, and sediment loads.
Appears in 1 contract