Automatic Temperature Controls Clause Samples
Automatic Temperature Controls. 1. Building will be provided with a new computer based automatic temperature control system (DDC) that will control multiple functions/systems to maintain proper environmental conditioners at all times.
2. The rooftop air handling units will be provided with controls to discharge air temperature, modulate supply, return and outside air volume, control and optimization of energy management as appropriate.
3. Zones will be controlled to specified temperature through local zone sensors.
4. Exhaust fans will be interlocked to run with associated supply air handling unit.
Automatic Temperature Controls a. The building will be equipped with a new computer based energy management system (EMS) providing automatic temperature controls that will control multiple functions/systems to maintain efficient environmental conditions at all times. Zones are controlled to specified temperature by the energy management system through local thermostats / zone sensors.
Automatic Temperature Controls. 1. The building control system shall be, in general, a pneumatic system. Building automation system shall be an electronic microprocessor based system employing direct digital control technology. Each main air handling system and each water system shall be provided with a separate DDC cabinet.
2. System shall be able to start and stop all equipment remotely and monitor and reset from a remote location air system supply air temperatures, outside air temperatures, fan discharge temperature, return air temperatures, supply and return temperatures of all water systems with reset of supply water temperatures. In addition to points required for the operations building allow five hundred (500) points for data center.
3. System shall provide alarms for all off-normal conditions and status of remotely controlled motors by either pressure or flow switches.
4. System graphics shall be provided for each system.
5. System shall remotely control each supply air and each return air automatic damper in the duct taps at each floor from a central location both for part load operation and smoke control.
Automatic Temperature Controls. DDC and Bac Net Systems.