Temperature Rise Clause Samples

Temperature Rise. Rated temperature rise above 40 degrees C ambient temperature measured by resistance at service factor load of 1.15 shall not exceed 90 degrees C.
Temperature Rise. The winding temperature rise for all motors, when operating at the nameplate horsepower, shall not exceed 80 Degrees Celsius. Where ambient temperatures greater than 40 Degrees Celsius is specified, the temperature rise shall be reduced in accordance with NEMA MG 1.
Temperature Rise. The temperature rise, as determined by resistance, of all motors, shall not exceed the following derated values:- Insulation class E B F H Temperature rise (K) 50 60 80 100
Temperature Rise. During the acceptance tests on the generator a temperature rise test is conducted as close as possible to full load and rated power factor.
Temperature Rise. The winding temperature rise for all motors, when operating at the nameplate horsepower shall not exceed 80 C.