System Quality. i. Seller’s Facility and equipment shall not cause excessive voltage excursions nor cause the voltage to drop below or rise above the extent of the range maintained by Company without Seller’s Facility. Seller’s Facility and equipment shall not cause excessive voltage flicker nor introduce excessive distortion to the sinusoidal voltage or current waves. ii. Excessive voltage excursions, excessive voltage flicker, and excessive distortion to the sinusoidal voltage or current waves shall be determined in accordance with the applicable sections of the Company’s most current Standard & Engineering Services Guideline, Electric Standard No. DR07-01, which Standard shall be provided to Seller by Company at Seller’s request. Failure by Seller to operate the Facility within the limits set forth in this Agreement and the referenced Standard may result in immediate disconnection by Company of Seller’s Facility from Company’s System. iii. The operating frequency of the Seller’s Facility shall not deviate more than +0.5 Hertz (“Hz”) or –0.7 Hz from a 60 Hz base. The Seller shall automatically disconnect the Facility from the Company’s System within 15 cycles if this frequency tolerance cannot be maintained. The Seller may reconnect when the Company’s System voltage and frequency return to normal range and the system is stabilized. iv. In accordance with IEEE 519 the total harmonic distortion (“THD”) voltage shall not exceed 5.0% of the fundamental 60 Hz frequency nor 3.0% of the fundamental frequency for any individual harmonic when measured at the Point of Interconnection with the Company’s System.