Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels of substation/switchyard: Extension of 400/220 kV Jam Khambhaliya PS (GIS) One and Half Breaker Double Main Scheme Notes: - i) For one and half breaker switching scheme, any double circuit line consisting of two numbers of feeders and originating from the same transmission or generating switchyard shall not be terminated in one diameter.
Appears in 2 contracts
Sources: Transmission Service Agreement, Transmission Service Agreement
Switching Scheme. The switching schemes, as mentioned below, shall be adopted at various voltage levels of substation/switchyard: Extension of 400/220 765/400 kV Jam Khambhaliya PS Mahape S/s (GIS) One and Half Breaker One and Half Breaker Double Main Scheme Notes: -
i) For one and half breaker switching scheme, any double circuit line consisting of two numbers of feeders and originating from the same transmission or generating switchyard shall not be terminated in one diameter.
Appears in 1 contract
Sources: Transmission Service Agreement