STRAINER. The strainer shall be flanged and shall have effective straining area at least double the meter case inlet area. The body shall be bronze, and the strainer screen shall be stainless steel. The strainer shall be designed to operate at a minimum working pressure of 150 psi.
STRAINER. A strainer shall be provided for the disc meter. It shall be easily removable and have an effective straining area of double the disc meter inlet. Registration accuracy over the normal operating range shall be 98.5% to 101.5%. Registration at the crossover shall not be less than 95% with direct reading registers. Registration at the crossover shall not be less than 90% with absolute encoder or generator remote registers. Registration at the extended low flow rate shall not be less than 95%. • Type A — all meters shall be equipped with encoder remote registers per AWWA C707 and shall meet all AWWA C702 performance standards. • Type B — all meters shall be equipped with generator remotes per AWWA C706, shall meet all AWWA C702 performance standards and shall include all hardware. Two-wire cable shall not be included in quoted meter prices.
STRAINER. A single strainer is used to remove impurities from the gas. A pressure switch which monitors the differential across the strainer will signal an alarm through the gas turbine control system when the pressure drop across the strainer indicates cleaning is required.