Common use of Registration Accuracy Clause in Contracts

Registration Accuracy. The meters shall meet the following requirements for accuracy when tested with potable water at a minimum temperature of 80˚F. At any rate of flow within the normal test flow limits the meters shall register not less than 98.5% and not more than 101.5% of the water actually passed through the meter. At the minimum test flow rate the meters shall register not less than 95% and not more than 101% of the water actually passed through the meter.

Appears in 1 contract

Sources: Invitation to Bid

Registration Accuracy. The meters shall meet the following requirements for accuracy when tested with potable water at a minimum temperature of 80˚F. At any rate of flow within Registration accuracy over the normal test flow limits the meters operating ranges shall register not less than be 98.5% and not more than to 101.5% of %. Meters shall be factory tested for accuracy. A factory test tag certifying the water actually passed through the accuracy shall be provided for each meter. At The factory test tag must include the minimum test flow rate the meters shall register not less than 95% meter serial number and not more than 101% date of the water actually passed through the metermanufacture.

Appears in 1 contract

Sources: Invitation to Bid

Registration Accuracy. The meters shall meet the following requirements for accuracy when tested with potable water at a minimum temperature of 80˚F. At any rate of flow within Registration accuracy over the normal test flow limits operating range shall be 98.5% to 101.5%. Registration at the meters crossover shall register not be less than 98.597% for 2”, 3” and 4” sizes shall not more than 101.5% of the water actually passed through the meter. At the minimum test flow rate the meters shall register not be less than 95% and for the 6” size. Registration at the low flow rate shall not more be less than 101% of the water actually passed through the meter95%.

Appears in 1 contract

Sources: Invitation to Bid

Registration Accuracy. The meters shall meet the following requirements for accuracy when tested with potable water at a minimum temperature of 80˚F. At any rate of flow within Registration accuracy over the normal test flow limits the meters operating range shall register not less than be 98.5% and not more than to 101.5% of the water actually passed through the meter. At the minimum test flow rate the meters shall register not less than 95% and not more than 101% of the water actually passed through the meter%.

Appears in 1 contract