Reactive Power Absorption. The Facility shall also be capable of dynamically absorbing 0.23 MVARs from the transmission system for each MW supplied at the 230 kV Interconnection Point during simulations when the Facility is tested at 104% of nominal voltage. Simple Cycle combustion turbines used as peaking generation may be exempted from the MVAR absorption requirements.
Appears in 3 contracts
Samples: Interconnection Agreement (Southern Power Co), Interconnection Agreement (Southern Power Co), Interconnection Agreement (Southern Power Co)
Reactive Power Absorption. The Facility shall also be capable of dynamically absorbing 0.23 MVARs from the transmission system for each MW supplied at the 230 500 kV Interconnection Point during simulations when the Facility is tested at 1041.05% of nominal voltage,. Simple Cycle combustion turbines used as peaking generation may be exempted from the MVAR absorption requirements.
Appears in 1 contract
Reactive Power Absorption. The Facility shall also be capable of dynamically absorbing 0.23 MVARs from the transmission system for each MW supplied at the 230 500 kV Interconnection Point during simulations when the Facility is tested at 104105% of nominal voltage. Simple Cycle combustion turbines used as peaking generation may be exempted from the MVAR absorption requirements.
Appears in 1 contract
Samples: Interconnection Agreement (Tenaska Georgia Partners Lp)
Reactive Power Absorption. The Facility shall also be capable of dynamically absorbing 0.23 MVARs from the transmission system for each MW supplied at the 230 kV Interconnection Point during simulations when the Facility is tested at 1041.05% of nominal voltage,. Simple Cycle combustion turbines used as peaking generation may be exempted from the MVAR absorption requirements.
Appears in 1 contract