Interconnection Relaying. Applicant shall not energize, or de-energize, GTC’s equipment. The necessary control devices shall be installed by Applicant on the Generating Facility to prevent the energization of de- energized GTC’s equipment by Generating Facility. GTC shall have relaying at the Point of Interconnection, and Applicant must insure that its generating facility is disconnected from the GTC Interconnection Facilities whenever the Point of Interconnection is de-energized. GTC may re-energize the Point of Interconnection by remote control and GTC shall not be responsible for damage to Generating Facility due to an out of phase condition during re-energization.
Appears in 2 contracts
Sources: Interconnection and Operation and Maintenance Agreement, Interconnection and Operation and Maintenance Agreement
Interconnection Relaying. Applicant shall not energize, or de-energize, GTC’s equipment. The necessary control devices shall be installed by Applicant on the Generating Facility to prevent the energization of de- energized GTC’s equipment by Generating Facility. GTC shall have relaying at the Point of Interconnection, and Applicant must insure that its generating facility is disconnected from the GTC Interconnection Facilities System whenever the Point of Interconnection is de-energized. GTC may re-energize the Point of Interconnection by remote control and GTC shall not be responsible for damage to Generating Facility due to an out of phase condition during re-re- energization.
Appears in 1 contract
Sources: Interconnection and Operation and Maintenance Agreement