Hydrostatic Testing Sample Clauses

The Hydrostatic Testing clause requires that certain equipment, such as pipelines or pressure vessels, be filled with water and pressurized to a specified level to verify their structural integrity and leak-tightness before being put into service. This process typically involves maintaining the test pressure for a set period and inspecting for any drops in pressure or visible leaks. The core function of this clause is to ensure safety and compliance by confirming that the equipment can safely operate under expected pressures, thereby preventing failures and potential hazards during actual use.
POPULAR SAMPLE Copied 1 times
Hydrostatic Testing. 12.1 C/CT Company facilities shall be hydrostatically tested to demonstrate the structural integrity of the piping system and to prove that no leaks exist. Sections of the piping system which are of different design pressures shall be tested independently to at least the test pressures established by this section. 12.2 The test pressure for the C/CT Company facilities for systems operating at a hoop stress greater than 30% of SMYS, shall range between a maximum of 1.55 times the MAOP and a minimum of 1.5 times the MAOP for 8 hours. (Unless facilities are to be located in the State of New York where the duration will be 12 hours). 12.3 Facilities operating below 30% SMYS and above 100 psig (below 20% if in New York) shall be leak tested between a maximum 1.55 times the MAOP and a minimum of 1.5 times the MAOP for one hour or until it is determined that there are no hazardous leaks, whichever is greater. 12.4 For facilities located in a Class 4 location the test medium may only be water. 12.5 Systems having design pressures at or less than 100 psig shall be leak tested in accordance with D.O.T. 12.6 Caution shall be exercised during testing to insure that valves are in a half-open position when tested at pressures in excess of their maximum working pressure. 12.7 All instrumentation piping and tubing shall be leak tested as per D.O.T. 12.8 Upon completion of the hydrostatic test, the C/CT Company shall forward a copy of hydrostatic test report to ANR's Area Manager with the letter of certification. (See Section 17.0). The report shall list the types of pressure/temperature equipment and a copy of the charts. ENGINEERING SPECIFICATION NO. ES-20 STANDARD FOR CUSTOMER/CUSTODY TRANSFER COMPANY FACILITIES ON ANR OWNED PROPERTY -------------------------------------------------------------------------------- 12.9 Hydrotest waters shall be removed from property and disposed of in accordance with Federal, State, and Local Codes. A copy of disposal records shall be forwarded to ANR's Area Manager. Hydrotest water shall not be discharged on ANR or adjacent property.
Hydrostatic Testing. The Engineer shall witness all hydrostatic tests and the Manufacturer shall give at least one week notification to the Engineer of the proposed dates for such tests. Valve bodies shall be close ended tested to 2 x working pressure. Test pressures shall be maintained for at least 5 minutes and valve bodies shall be water tight in all respects. Assembled valves shall be open-ended tested to 1.5 x working pressure for material strength and soundness. Valves shall be drop tight over the complete range of pressures from 0 to 1.5 x working pressure. Each valve shall be supplied with a test certificate certifying that it complies in all respects with the requirements of this Specification.
Hydrostatic Testing a. Before any hydrant mains are turned off we recommend an authorised person from the company or premises assist with an inspection of the fire service, so a timetable can implemented for the purpose of minimising the risk in areas which cannot be shut down due to operational and safety to employees on site while working. b. Pressure testing of the fire hydrant service pipe work to the required design standard can cause some systems to fail or burst under pressure and we encourage all our customers to take the appropriate action in notifying their insurance company, employees, contractors, on the day of the test. Fire Boar accepts no liability whatsoever for system failure caused by the test and any damage caused as a result of the performance of the test, regardless of anything else stated in this agreement and regardless of any act or omission by Fire Boar. This quotation does not allow for the repairing of any pipe work or valves which leak while conducting the pressure testing procedure. c. Servicing of any underground check valves or isolating valves which may be installed in a pit are excluded from this quotation and will be quoted separately, unless otherwise stated in the quotation. d. Servicing of any underground check valves or isolating valves which may be installed in a pit are excluded from this quotation and will be quoted separately, unless otherwise stated in the quotation.
Hydrostatic Testing a) Hydrostatic testing shall be conducted per the applicable specification and/or requirement, and shall be accomplished prior to certification. b) The test data shall be maintained by the contractor and the actual results submitted to the CA. c) The hydrostatic and post-test inspection of the part/assembly for leaks and damage shall occur on the same day. – Hydrostatic Pressure Testing – Joint Tightness TestingDynamic Testing.
Hydrostatic Testing. The Certificate Holder shall conduct a 24-hour hydrostatic pressure test at least 150% of the maximum allowable operating pressure (MAOP) for the two segments of the Pipeline. The segment from the Canadian border to the pressure regulating station will be tested at at least 1200 psig, and the segment from the pressure regulating station to the Generation Facility shall be tested at at least 750 psig. Hydrostatic test water shall be used and discharged according to the requirements of Article IV.M.3 of this Agreement.
Hydrostatic Testing. All hydrostatic testing shall be performed in accordance with NFPA, Federal, State and local codes and standards. Hydrostatic testing shall be done every 12 years for the dry chemical type extinguishers and every 5 years for the CO2 type extinguishers.
Hydrostatic Testing. After flushing system, test fire sprinkler piping hydrostatically, for period of 2 hours, at not less than 200 PSI or at 50 PSI in excess of maximum static pressure when maximum static pressure is in excess of 150 PSI. Check system for leakage of joints. Measure hydrostatic pressure at low point of each system or zone being tested. A. Dry-Pipe Testing - Test dry-pipe hydrostatically except, in freezing conditions, test with air at pressures not less than 50 PSI, for a period of 2 hours. Check system for leakage. Leave differential dry-valve clappers open during test, to prevent damage. B. Repair or replace piping system as required to eliminate leakage in accordance with NFPA standards for "little or no leakage" and retest as specified to demonstrate compliance.
Hydrostatic Testing external and internal examination of the cylinders and pressure testing of the fire extinguishers using water or some other non-compressible fluid to help prevent rupture of the cylinder. Hydrostatic Testing shall be completed at the following intervals: • Pressurized water, carbon dioxide, and wet chemical extinguishers – every 5 years • Dry chemical extinguishers – every 12 years.
Hydrostatic Testing. Furnish necessary material, equipment, and labor for testing including pump, water storage vessel, piping, pressure gage, valve, hydrant, and corporation stop.

Related to Hydrostatic Testing

  • Random Testing Notwithstanding any provisions of the Collective Agreement or any special agreements appended thereto, section 4.6 of the Canadian Model will not be applied by agreement. If applied to a worker dispatched by the Union, it will be applied or deemed to be applied unilaterally by the Employer. The Union retains the right to grieve the legality of any imposition of random testing in accordance with the Grievance Procedure set out in this Collective Agreement.

  • Substance Abuse Testing The Parties agree that it is in the best interest of all concerned to promote a safe working environment. The Union has no objection to pre-employment substance abuse testing when required by the Employer and further, the Union has no objection to voluntary substance abuse testing to qualify for employment on projects when required by a project owner. The cost and scheduling of such testing shall be paid for and arranged by the Employer. The Union agrees to reimburse the Employer for any failed pre-access Alcohol and Drug test costs.

  • ODUF Testing 6.6.1 Upon request from TWTC, AT&T shall send ODUF test files to TWTC. The Parties agree to review and discuss the ODUF file content and/or format. For testing of usage results, AT&T shall request that TWTC set up a production (live) file. The live test may consist of TWTC’s employees making test calls for the types of services TWTC requests on ODUF. These test calls are logged by TWTC, and the logs are provided to AT&T. These logs will be used to verify the files. Testing will be completed within thirty (30) days from the date on which the initial test file was sent.

  • Drug Testing (A) The state and the PBA agree to drug testing of employees in accordance with section 112.0455, F.S., the Drug-Free Workplace Act. (B) All classes covered by this Agreement are designated special risk classes for drug testing purposes. Special risk means employees who are required as a condition of employment to be certified under Chapter 633 or Chapter 943, F.S. (C) An employee shall have the right to grieve any disciplinary action taken under section 112.0455, the Drug-Free Workplace Act, subject to the limitations on the grievability of disciplinary actions in Article 10. If an employee is not disciplined but is denied a demotion, reassignment, or promotion as a result of a positive confirmed drug test, the employee shall have the right to grieve such action in accordance with Article 6.

  • Meter Testing Company shall provide at least twenty-four (24) hours' notice to Seller prior to any test it may perform on the revenue meters or metering equipment. Seller shall have the right to have a representative present during each such test. Seller may request, and Company shall perform, if requested, tests in addition to the every fifth-year test and Seller shall pay the cost of such tests. Company may, in its sole discretion, perform tests in addition to the fifth year test and Company shall pay the cost of such tests. If any of the revenue meters or metering equipment is found to be inaccurate at any time, as determined by testing in accordance with this Section 10.2 (Meter Testing), Company shall promptly cause such equipment to be made accurate, and the period of inaccuracy, as well as an estimate for correct meter readings, shall be determined in accordance with Section 10.3 (Corrections).