Harmonics. The Generating Facility shall not introduce excessive distortion to GTC’s electric system’s voltage profile and current waveforms, in accordance with Article 7.8. The Generating Facility is required to meet the harmonic current and voltage distortion limits at the Point of Interconnection as specified in Tables 1 through 4 of IEEE Std. 519-2014, or any applicable superseding electric industry standard. The harmonic distortion measurements shall be made at the transmission facility serving the Generating Facility.
Appears in 3 contracts
Samples: Interconnection and Operation and Maintenance Agreement, Interconnection and Operation and Maintenance Agreement, Interconnection and Operation and Maintenance Agreement
Harmonics. The Generating Facility shall not introduce excessive distortion to GTCTransmission Provider’s electric system’s voltage profile and current waveforms, in accordance with Article 7.89.7.6. The Generating Facility is required to meet the harmonic current and voltage distortion limits at the Point of Interconnection as specified in Tables 10-4 and 11-1 through 4 of IEEE Std. 519-20141992, or any applicable superseding electric industry standardas revised. The harmonic distortion measurements shall be made at the transmission facility serving the Generating Facility.