Ground System Analysis Sample Clauses

Ground System Analysis. 7.1.3.1 The ground system analysis and design shall meet the recommendations, guidelines, and procedures of IEEE Standard 80, “Guide for Safety in Substation Grounding.” The Site specific geotechnical report does not contain soil resistivity data necessary for grounding system design. That information will be the responsibility of Contractor. 7.1.3.2 The Plant grounding grid and the ground grid of the 138kV switchyard must be coordinated and interconnected to create a single grid. All structures, including the buildings shall be effectively bonded to the ground grid.