EQUIPMENT PERFORMANCE REQUIREMENTS Sample Clauses
EQUIPMENT PERFORMANCE REQUIREMENTS. A. Equipment listing, type, and individual car performance requirements are covered under Appendix B of this Agreement. Equipment performance requirements indicated are the minimum standard and are not the sole criteria for judging the Contractor’s performance. Consistent failure to meet performance requirements may be grounds for termination.
B. Elevator Ride Quality:
1) Floor-to-floor times are measured in seconds from start of doors closing, including a typical one-floor travel and until the elevator is approximately level with the next successive floor, either up or down, and the doors are 3/4 open for center opening doors or 1/2 open for side opening doors based on the following requirements and shall maintain a smooth ride quality at all times. Deviation from these requirements shall only be allowed if permitted by code or County’s written approval. Times shown are ±0.2 seconds.
2) Door opening times are measured in seconds from start of car door open until doors are fully open. Times shown are ±0.1 seconds. Door closing times are measured in seconds from start of door close to doors fully closed, and shall be no less than the times shown per above schedule or those permitted by code. Times shown are ±0.1 seconds. Door closing force is measured at rest with the doors between 1/3 and 2/3 closed. Door closing force shall be no more than 30 lbf.
3) Stopping accuracy shall be measured under all load conditions and maintained within ¼” +/- between landing and car sill under any loading condition.
4) Variance from rated speed, regardless of load, shall not exceed the following:
EQUIPMENT PERFORMANCE REQUIREMENTS. A. Equipment listing, type, and individual car performance requirements are covered under Appendix B of this SOW. Equipment performance requirements indicated are the minimum standard and are not the sole criteria for judging Contractor’s performance. Consistent failure to meet performance requirements shall be grounds for cancellation of this Agreement.
B. Contractor shall maintain a quiet and comfortable car ride with smooth acceleration, deceleration, and accurate stop. Door operation shall be smooth and quiet.
EQUIPMENT PERFORMANCE REQUIREMENTS. A. Equipment listing, type, and individual car performance requirements are covered under Appendix A of this Agreement. Equipment performance requirements indicated are the minimum standard, and are not the sole criteria for judging Contractor’s performance. Consistent failure to meet performance requirements shall be grounds for cancellation of this Agreement.
B. Elevator Ride Quality: Horizontal and vertical acceleration within cars during all riding and door operating conditions shall not exceed 25 mg peak to peak in the 1 - 10 range; Measurement criteria ISO804.
C. Contractor shall maintain a quiet and comfortable car ride with smooth acceleration, deceleration and accurate stop. Door operation shall be smooth and quiet.
EQUIPMENT PERFORMANCE REQUIREMENTS. A. Equipment performance requirements are covered under Appendix B of this Contract. Equipment performance requirements indicated are the minimum standard and are not the sole criteria for judging Contractor’s performance. Consistent failure to meet performance requirements shall be grounds for cancellation of this Contract.
B. Elevator Ride Quality:
1. Horizontal and vertical acceleration within cars during all riding and door operating conditions shall not exceed 20 mg peak-to-peak in the 1 - 10 Hz range. Measurement criteria ISO804.
2. Acceleration and deceleration shall be smooth constant and not exceed 3 feet/second² with an initial ramp between 0.5 and 0.75 seconds.
3. Sustained jerk shall not exceed 6 feet/second³.
4. Noise level shall not be disruptive to building operation.
C. Measured noise levels in a moving car outside the leveling zone shall not exceed 55 dBA under any condition including car ventilation blower or fan on highest speed. Measured noise levels in car within the leveling zone or when car is stopped shall not exceed 60 dBA. There shall be no discernible sound in the elevator car from hoist machine, suspension means, sheaves, counterweight, pump unit, electrical power conversion units, platforms, car enclosure walls, or car and counterweight guide assemblies unless it is mutually determined by Contractor and County that such sounds are attributable to the design of the equipment, provided such design exception shall not apply to the extent that Contractor has provided design or redesign services under this Contract.
D. Contractor shall maintain a quiet and comfortable car ride with smooth acceleration, deceleration, and accurate stop. Door operation shall be smooth and quiet.