Electrical test Sample Clauses

Electrical test. On completion of wiring, the whole installation will be tested in accordance with IS- 732, clause 8(a) (b) & (c) and test certificate as per Appendix ‘B’ of the above IS rendered duly signed by the contractor and Engineer-in-Charge. If the test results are not acceptable, all repairs and replacement and extra work of removal and relaying of re fixing shall be carried out by the contractor at his own expense and installation retested, until test result indicate compliance with the pre scribed requirement. The contractor shall supply all necessary apparatus, lab and instruments or equipments required for testing. The quoted rate for Sch ‘A’ shall be deemed to include for the above provision.
Electrical test according to IEC 60227-2 1. Resistance of conductors. Sub clause 2.1. 2. Insulation resistance at 70 °C. Sub clause 2.2. 3. Voltage test at 2 500 V. Sub clause 2.4.
Electrical test according to IEC 60502-1 a) Insulation resistance measurement at ambient temperature. Sub clause 17.2. b) Insulation resistance measurement at maximum conductor temperature in normal operation. Sub clause 17.3. c) Voltage test for 4 h. Sub clause 17.4.