Conductors. WinStar Wireless, Inc. Hub Facility AC Power System conductor requirements must conform to the following parameters: All conductors are to be AWG type THHN insulated copper only. All conductor termination's are to be performed utilizing Compression (15) Ton High-Press, Hex or Circumventual Crimps will only be accepted. All termination's are to utilize (2) Hole NEMA Spaced Long Barrel Lugs only. All fastening hardware to be #316 Grade Stainless Steel only. All termination's are to be insulated utilizing Thick Wall Heat Shrink. All conductors are to be permanently identified utilizing Fiber Cable Tags only.