Conductors Sample Clauses

Conductors. Conductors shall consist of a stranded aluminum wires, as detailed elsewhere in the specification. They shall comply with latest IEC publication 60228. Non circular conductors shall be pre spiraled and compacted.
AutoNDA by SimpleDocs
Conductors. The contractor is required to test cap cable(s) during installation as part of the cable item.
Conductors. Item 44(a) Furnish and install #12 AWG XLP Copper conductor cable (600V). Item 44(b) Furnish and install #6 AWG XLP Copper conductor cable (600V). Item 44(c) Furnish and install #2 AWG XLP Copper conductor cable (600V). Item 44(c)1 Furnish and install #6 AWG XLP Aluminum conductor cable (600V). Item 44(d) Furnish and install #2/0 XLP Copper conductor cable (600V). Item 44(d)1 Furnish and install #4/0 XLP Copper conductor cable (600V). Item 44(e) Furnish and install #2 AWG EPR Copper conductor cable (15KV). Item 44(f) Furnish and install #2/0 AWG EPR Copper conductor cable (15kV). Item 44(g) Furnish and install 500 MCM EPR Copper conductor cable (15KV). Item 44(h) Furnish and install #4/0 AWG EPR Copper conductor cable (15kV).The Contractor shall furnish all labor, material, equipment, necessary to install cross linked polyethylene covered or EPR high voltage cable in conduit. All conductors run shall be continuous from box to box. The cable and method of installation shall be in accordance with these specifications. The work shall include but not be limited to the following:
Conductors. Item 44(a) - Furnish and install #12 AWG XLP Copper conductor cable (600V). Item 44(b) - Furnish and install #6 AWG XLP Copper conductor cable (600V). Item 44(c) - Furnish and install #2 AWG XLP Copper conductor cable (600V). Item 44(c)1 - Furnish and install #6 AWG XLP Aluminum conductor cable (600V). Item 44(d) - Furnish and install #2/0 XLP Copper conductor cable (600V). Item 44(d)1- Furnish and install #4/0 XLP Copper conductor cable (600V). Item 44(e) - Furnish and install #2 AWG EPR Copper conductor cable (15KV). Item 44(f) - Furnish and install #2/0 AWG EPR Copper conductor cable (15kV). Item 44(g) - Furnish and install 500 MCM EPR Copper conductor cable (15KV). Item 44(h) - Furnish and install #4/0 AWG EPR Copper conductor cable (15kV).
Conductors. WinStar Wireless, Inc. Hub Facility AC Power System conductor requirements must conform to the following parameters: All conductors are to be AWG type THHN insulated copper only. All conductor termination's are to be performed utilizing Compression (15) Ton High-Press, Hex or Circumventual Crimps will only be accepted. All termination's are to utilize (2) Hole NEMA Spaced Long Barrel Lugs only. All fastening hardware to be #316 Grade Stainless Steel only. All termination's are to be insulated utilizing Thick Wall Heat Shrink. All conductors are to be permanently identified utilizing Fiber Cable Tags only.
Conductors. WinStar Wireless, Inc. Hub Facility DC Power System conductor requirements must conform to the following parameters: All conductors are to be AWG type THHN insulated copper only. All conductor termination's are to be performed utilizing Compression (15) Ton High-Press, Hex or Circumventual Crimps will only be accepted. All termination's are to utilize (2) Hole NEMA Spaced Long Barrel Lugs only. All fastening hardware to be #316 Grade Stainless Steel only. All termination's are to be insulated utilizing Thick Wall Heat Shrink. All conductors are to secured utilizing #9 Round Wax Lacing Cord only. All conductors are to be permanently identified utilizing Fiber Cable Tags only. All conductors are to be routed complete point to point. Use of Splices is prohibited. Cabling from main distribution board to equipment racks shall be supported below cable ladder using "J" hooks.
Conductors. Bundled or unbundled, 1033 MCM, Aluminum Conductor, Steel Reinforced (ACSR) cable. Strength requirements shall be in accordance with G.O. 95. Groundwire: One groundwire, approximately 0.5 inch in diameter, attached to the top of tower or pole.
AutoNDA by SimpleDocs
Conductors. Conductor shall be Stranded copper conductor class 2, according to IEC 60228.
Conductors. 2.1 Conductors will be paid one and one-half times their regular rate for all spare work performed outside their assignment. .
Conductors. 1. Conductor size for power circuits shall be minimum No. 12 AWG. Conductors No. 10 AWG and smaller shall be solid copper, 90°C, type THWN-2. Conductors larger than No. 10 AWG shall be stranded copper, 75°C THWN-2. The Shoppes at Springfield Commons Tenant’s Criteria Manual E. Convenience outlets
Time is Money Join Law Insider Premium to draft better contracts faster.