Conductors. WinStar Wireless, Inc. Hub Facility DC Power System conductor requirements must conform to the following parameters: All conductors are to be AWG type THHN insulated copper only. All conductor termination's are to be performed utilizing Compression (15) Ton High-Press, Hex or Circumventual Crimps will only be accepted. All termination's are to utilize (2) Hole NEMA Spaced Long Barrel Lugs only. All fastening hardware to be #316 Grade Stainless Steel only. All termination's are to be insulated utilizing Thick Wall Heat Shrink. All conductors are to secured utilizing #9 Round Wax Lacing Cord only. All conductors are to be permanently identified utilizing Fiber Cable Tags only. All conductors are to be routed complete point to point. Use of Splices is prohibited. Cabling from main distribution board to equipment racks shall be supported below cable ladder using "J" hooks.