AND CONDUCTORS. Generally, wiring will consist of insulated conductors installed in 3/4" minimum size, EMT. Flexible conduit (BX) will be used for terminal connection at all motors. Electrical metallic tubing will be used in areas above hung ceilings. Aluminum conduit may be used in concealed areas or in areas eight feet (8') above the floor. No aluminum conduit will be used in concrete or underground. BX may be used where allowed by applicable codes. Above the ceiling is used as a return air plenum. Conductors will be 600 volt copper, except where otherwise noted. Wire/cable #2 and larger may be aluminum. The following conductors will be used: