Unit Heat Rate definition
Examples of Unit Heat Rate in a sentence
The Net Unit Heat Rate Test results will be considered the numerical average of the consistent individual tests for each condition.
The Avoided Unit Energy Cost, in cents per kilowatt - hour (¢/kWh) shall be defined as the product of (a) the Avoided Unit Fuel Cost and (b) the Avoided Unit Heat Rate; plus (c) the Avoided Unit Variable O&M.
The Unit Power Output Test, and Unit Heat Rate Test, the Maximum Unit Power Output Test and the Auxiliary Load Test (herein referred to as "Performance Tests") shall be conducted by Contractor to demonstrate that the respective performance guarantees are met.
The Commercial Tolerance Bands for Unit Power Output and Unit Heat Rate are based on the assumed accuracies of the Owner's electrical meter and the fuel supply meter as defined Section 2.1.
Contractor further agrees that if a Unit does not achieve the Net Unit Heat Rate Guarantee, as calculated in accordance with Exhibit I-2, Contractor shall pay liquidated damages to Owner in the amount of *** Dollars ($***) per Btu/kilowatt hour for each Btu/kilowatt hour by which such Unit exceeds the Net Unit Heat Rate Guarantee.
Preliminary results for the Unit Heat Rate Test shall be based on fuel characteristics obtained from samples taken prior to such tests, Contractor shall provide a formal Acceptance Test Report promptly but no later than 14 days following the completion of such tests.
During the Unit Heat Rate Test, a minimum of three (3) gas fuel samples per hour shall be taken for chromatographic analysis as per ASTM D 1945.
Unit Power Output (for both the Unit Power Output Test, and the Maximum Unit Power Output Test) and Unit Heat Rate for each Unit shall be the average of results from the four one-hour test periods.
Contractor and Owner shall document the adjusted Net Unit Capacity Guarantees and Net Unit Heat Rate Guarantees in writing, which shall be signed by duly authorized representatives of both such Parties.
A test result for Unit Heat Rate that is within plus or minus 1.0 percent of the applicable guaranteed Unit Net Heat Rate as set out in Section 6 of the Second Schedule (Operating Parameters) shall be deemed to indicate exact compliance with such guaranteed Unit Net Heat Rate.